6 Ventilation mode change recommendation (RECOMMENDED, VENTILATION MODE) display
When using PZ-60DR-E and the ventilation mode is set to Lossnay ventilation or bypass ventilation, "REC-
OMMENDED" and "VENTILATION MODE" may be displayed alternately (for 10 minutes maximum). This
function informs the user of the suitable ventilation mode according to the automatic ventilation algorithm.
When a ventilation mode change recommendation has been displayed, more comfortable ventilation can be
provided by pressing the "Function selector" button of the remote controller and switching to another ventila-
tion mode.
(We recommend that "AUTO" be selected for the ventilation mode; however, there is no problem in leaving
the ventilation mode unchanged with "RECOMMENDED" "VENTILATION MODE" displayed.)
(5) Interlocking with external devices
1 Input signal
The system will interlock with the following input signals from external devices and start/stop.
systems having multiple Lossnay units, input the signal to the "Main" Lossnay.
Multiple units
Type
Level signal
Charged 12 V DC/24 V DC
Operation signal: 12 V DC/24 V DC
Stop signal
Uncharged a-contact
(Current drawn: 10 mA or greater)
Operation signal: Close
Stop signal
Pulse signal
Charged
Uncharged a-contact
Start/stop is inverted with each
pulse
Systems
• Connect the signal cable of Mr. Slim to Lossnay, and per-
interlocked
form the Lossnay interlock settings from the A-control
with Mr.
remote controller or the K-control remote controller.
Slim
• The system is started/stopped by interlocking with
Start/Stop of the A-control remote controller or K-control
remote controller.
• The system is started/stopped by interlocking with the venti-
lation setting of the A-control remote controller.
• The Mr. Slim operation mode, target temperature, and other
internal information can also be brought in.
Systems
• City Multi indoor units and Lossnay are connected by M-
interlocked
NET, and the Lossnay interlock setting is performed from
with
the remote controller or system controller.
Mitsubishi
• The system is started/stopped by interlocking with
City Multi
Start/Stop of the MA remote controller or ME remote con-
indoor units
troller and the ventilation setting.
• The City Multi indoor unit operation mode, target tempera-
ture, and other internal information can also be brought in.
Signal, and operation
: 0 V
: Open
12 V DC/24 V DC
Pulse width 200 ms or greater
— 31 —
Setting Method
PZ-60DR-E
PZ-60DR-E Not Used
(Remote controller
(Function selec-
function selection)
tion switch)
Pulse input setting
SW2-2: OFF
"oFF"
Pulse input setting
SW2-2: ON
"on"
PZ-60DR-E
SW2-2: OFF
(Lossnay remote
controller) can-
not be used.
Pulse input setting
SW2-2: OFF
"oFF"