P40 Gas Fireplace

Framing and Finishing

1)
Frame the enclosure for the unit with framing material. Use the
determined total thickness of facing material (e.g. drywall plus
ceramic tiles) to adjust the framing depth to allow the fi nished
surface to be fl ush with the front of the unit. Total facing thickness
can vary from 1/2" (13mm) to 1-1/4" (32mm) thick.
Note: Header for the P40 must be non combustible.
2)
For exterior walls, insulate the enclosure to the same degree as
the rest of the house, apply vapor barrier and drywall, as per local
installation codes. (Do not insulate the fi replace itself.)
3)
Ensure that all of the clearances listed below are met. Combustible
material may be brought up to the sides of the unit and be covered
with ceramic tiles, bricks, rock or other suitable combustible
fi nishing materials. Non-combustible facing is required above
the unit. (See Dimension "N" on page 41)
Note: You must maintain proper clearances from the vent to
combustible materials (See Below).
4)
Use metal studs for framing where the minimum clearance from
the vent to combustible material cannot be maintained.

Clearance Requirements

Required hearth must be non-combustible. (Page 43)
Required non-combustible facing above unit. (See Dimension
"N" on page 41)
D
C
A
B
I
G
Clearance:
Dimension
A: Mantel Height
12" (305mm)
B: Sidewall
8" (203mm)
C: Ceiling
39" (991mm)
D: Mantel Depth
13" (330mm)
E: Alcove Width
56" (1422mm)
F: Alcove Depth
36" (914mm)
G: Hearth Height
1-1/2" (39mm)
H: Hearth Width
40" (1016mm)
I: Hearth Depth
16" (406mm)
46
F
B
H
E
Measured From:
Minimum (Additional on this page)
Side of installed front
Top of installed unit
Maximum (Additional on this page)
Sidewall to Sidewall (Minimum)
Front to back wall (Maximum)
Floor to top of Hearth.
(Hearth must
not be higher than base of fi rebox.)
Edge to Edge of Hearth
Front of Hearth to Wall
Gas Fireplaces
Vent Clearances
Horizontal - Top
Horizontal - Side
Horizontal - Bottom
Vertical (Flex or Rigid)
WARNING
Failure to maintain required clearances is a major cause of
chimney related fi res. Installation of this fi replace must comply
with these clearances.

Hearth Requirements

A 40" (1016mm) wide x 16" (406mm) deep x 1-1/2" (38mm) thick hearth
is required, unless the unit is raised 4" (102mm).
All measurements are from the bottom of the unit. Therefor the
bottom of the unit would be fl ush with the top of a non-combustible
hearth or 4" above the surface of a combustible fl oor.
Floor Mounted Fireplace
Raised Fireplace
Full Screen Door Facing Requirements
10-1/4" Above Fireplace
6"
6"
June 2007 Regency Product Specifi cations Book
Clearance Dimension
2-1/2" (64mm)
1-1/2" (38mm)
1-1/2" (38mm)
1-1/4" (32mm)
WARNING: When installing the
Full Screen Doors
The Full Screen Front requires
additional non combustible facing
and non-combustible framing.
Ensure the 10-1/4" above the
fi replace, 6" on both sides and
both the header and side studs
are non-combustible materials.
All other clearances, including
mantel, remain the same.