Current Transformer:
Should input current exceed rated current tolerated by the meter
specifications, the power meter needs to be used together with a current
transformer (CT). Users can select a suitable CT according to the table
below.
Primary
Model
Current (A)
DCT-S301C
100A
DCT-S211C
200A
DCT-S221C
300A
DCT-S231C
400A
DCT-S241C
500A
DCT-S251C
600A
DCT-S261C
750A
DCT-S271C
1000A
DCT-S281C
1500A
DCT-S291C
2000A
DCT-S2A1C
2500A
DCT-S2B1C
3000A
*All models are not UL-certified.
Notes on selecting a current transformer
1. For the current transformer, the model with a closer maximal current on the primary side should be
selected according to the maximal current actually input.
For example: When the maximal current input is 700 A, DCT-S261C can be selected.
2. Wire over-length on the secondary side of the current transformer causes decrease in accuracy.

Appendix

Secondary
Burden (VA)
Current (A)
5A
1.5VA
5A
1.5VA
5A
2.5VA
5A
3.75VA
5A
5VA
5A
5VA
5A
5VA
5A
10VA
5A
10VA
5A
10VA
5A
15VA
5A
20VA
Accuracy (%)
1.0%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
82
Size (mm)
Outer frame
Inner frame
Outer frame
Inner frame
Outer frame
Inner frame
Outer frame
Inner frame
Outer frame
145*116*51
Inner frame
Outer frame
145*116*51
Inner frame
Outer frame
145*116*51
Inner frame
Outer frame
145*116*51
Inner frame
Outer frame
196*146*51
Inner frame
Outer frame
250*186*51.4
Inner frame
160.5*81*32
Outer frame
250*186*51.4
Inner frame
160.5*81*32
Outer frame
250*186*51.4
Inner frame
160.5*81*32
115*89*51
32*21*32
115*89*51
32*21*32
115*89*51
32*21*32
115*89*51
32*21*32
80*50*32
80*50*32
80*50*32
80*50*32
122*80*32