TECHNICAL DATA

SPECIFICATIONS

Fuel
F3 Firing rate - Effective Output
F5 Firing rate - Effective Output
Voltage (single phase)
F3 Absorbed electrical power
F5 Absorbed electrical power
Motor (rated)
Capacitor
Pump pressure
Primary control
Ignition transformer

BURNER AND MOUNTING FLANGE DIMENSIONS

Model
A
Inches
8 15/32
9 59/64
F3
mm
215
Inches
9 11/64
10 11/16
F5
mm
233
E1: 10-inch long (254mm) tubes are also available.

BURNER COMPONENTS IDENTIFICATION

1
2
3
4
8
17
16
15
3222
No. 2 Fuel Oil
0.50 to 0.95 US GPH - 70,000 to 133,000 BTU/h
0.75 to 1.65 US GPH - 105,000 to 231,000 BTU/h
230v 50 Hz
175 Watts
264 Watts
2800 rpm Run Current 0.8 AMP
12.5 Microfarads
130 to 200 psig
RIELLO 530 SE/C - RIELLO 530 SE/C 24V
8kV 16mA
B
C
D
6 15/32
3 1/2
252
164
89
7 3/32
3 1/2
272
180
89
9
10 11
E
F
6
8 29/32
152
226
6
9 13/32
152
239
7
6

BURNER COMPONENTS

5
1
Lockout indicator lamp and reset button
2
Primary control
3
Primary control sub-base
18
4
Pump pressure regulator
5
Motor
6
Air adjustment fixing screws
12
7
Capacitor
8
Combustion Head
13
9
Semi Flange
10
Turbulator adjustment screw
11
Air tube cover
12
Coil
13
Vacuum gauge port
14
Pressure gauge and bleeder port
14
15
Return fuel line port
16
Supply fuel line port
17
Mounting flange with gasket
18
24V thermostat connections
(only 530 SE/C 24V)
D8799
GB
B
E
F
E1
D7352
5 1 / 2 "-140mm
7 1 / 2 " - 190 mm
8 15 / 32 " - 215 mm
D7351
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

40 f5