BURNER ADJUSTMENT TABLE

NON-RETROFIT APPLICATIONS
If this burner is being installed in a packaged unit (i.e. Burner comes with a boiler or furnace), follow the instal-
lation and set-up instructions supplied with the heating appliance, as settings will differ from those shown in
this manual.
Actual firing
rate 5% ±
US GPH
0.50
0.60
0.75
0.80
0.95
Actual firing
rate 5% ±
US GPH
0.75
0.85
1.00
1.10
1.25
1.50
1.65
The above set up charts are a starting point only.
The burner and appliance must be properly set up using proper combustion testing equipment.
Any approved oil burner nozzle type, angle and manufacturer maybe used, as long as input is cor-
WARNING
responding the correct BTU/hr or US gph input rating of the appliance.
COMBUSTION CHAMBER
Follow the instructions furnished by the boiler/furnace manufacturer. Size retrofit application according to the appropri-
ate installation codes (e.g. CSA B139 or NFPA #31).
3222
MODEL F3 BURNER
Nozzle
size
GPH
PSI
.40 x 60º/80º
160
.50 x 60º/80º
150
.60 x 60º/80º
150
.65 x 60º/80º
150
.75 x 60º/80º
160
MODEL F5 BURNER
Nozzle
size
GPH
PSI
.60 x 60/ 80º
145
.65 x 60/ 80º
145
.85 x 60/ 80º
145
1.00 X 60/ 80°
145
1.10 x 60/ 80º
145
1.25 x 60/ 80º
145
1.35 X 60/ 80°
145
Pump
Turbulator
pressure
bar
11.0
10.4
10.4
10.4
11.0
Pump
Turbulator
pressure
bar
10
10
10
10
10
10
10
Air damper
setting
setting
0.0
2.3
0.5
2.7
1.5
3.4
2.0
3.6
3.0
4.3
Air damper
setting
setting
0.0
2.25
0.5
2.5
1.0
2.75
2.0
3.0
2.5
3.5
3.0
4.25
4.0
6.0
GB
12