18.2.11 Low Pressure Protection (F31-01)
Malfunction Decision Conditions
During operation of cooling and heating, when the outdoor unit low pressure sensor saturated temperature value
detected < 45°C.
Malfunction Caused
Clogged air filter of indoor unit.
Dust accumulation on the indoor/outdoor unit heat exchanger.
Air short circuit at indoor/outdoor unit.
3 way valve closed.
Faulty outdoor unit fan motor.
Refrigerant shortage (refrigerant leakage).
Clogged expansion valve or strainer.
Faulty outdoor unit low pressure switch.
Faulty outdoor unit PCB (main).
Abnormality Judgment
Continue 7 times in 60 minutes.
Troubleshooting