Panasonic S-22KA1E5S Service Manual page 110

Ka1e5 series, ya1e5 series, ua1e5 series, na1e5 series, ma1e5 series,
Hide thumbs Also See for S-22KA1E5S:
Table of Contents

Advertisement

Carry out Earthing work.
Do not connect the Earth return to the gas pipe, water line pipe, lightning rod and telephone lines.
Imperfection in Earth return may lead to electric shock
Do not install the unit at the place where the possibility of inflammable gas leakage exists. If gas leakage should arise and the gas builds
up around the unit, such situation may lead to ignition.
Mounting of the earth leakage circuit breaker is required. Omission in mounting of the earth leakage circuit breaker may lead to electric
shock.
Drain piping should be made to ensure secure drainage according to the manual for installation work and carry out the thermal insulation
to prevent the occurrence of condensation.
Imperfection in piping work leads to water leakage and may cause the house and property, etc. to become wet.
Position the indoor unit, outdoor unit, power cords and indoor/outdoor unit connection cables in a way so that they are at least 1 meter
away from televisions and radios. This is to avoid problems such as interference with picture and/or sound. (However, note that
depending on the electromagnetic wave conditions, interference may still occur even if the separation distance is more than 1 meter.)
11.6.1 ACCESSORIES PACKED IN THE INDOOR UNIT CONTAINER
Name
Plate
Screw
Installation Instruction
11.6.2 SELECTING THE LOCATION FOR THE INDOOR UNIT
Install the indoor unit once the following conditions are satisfied and after receiving the customer approval.
1. The indoor unit must be within a maintenance space.
2. The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spreading
of air throughout the room.
3. The installation position must be able to support a load four times the indoor unit weight.
4. The indoor unit must be away from heat and steam sources, but avoid installing it near an entrance.
5. The indoor unit must allow easy draining.
6. The indoor unit must allow easy connection to the outdoor unit.
7. Before installing in quiet room such as a bedroom, please consult with an authorized distributor.
8. The indoor unit must be from at least 3m away from any noise-generating equipment. The electrical wiring
should be locally decided.
9. If the power supply is subject to noise generation, add a suppressor.
10. Do not install the indoor unit in a laundry. Electric shocks may result.
Cautions
Q'ty
Appearance
1
5
1
100 or more
Floor
Warnings
Installation plate fixing screw
This manual
(Unit: mm)
50 or more
110
Purpose

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents