EMC, LOW VOLTAGE, AND MACHINERY DIRECTIVES

9.2.3 Power supply

The insulation specification of the power supply module was designed assuming
installation category II. Be sure to use the installation category II power supply to the
programmable controller.
The installation category indicates the durability level against surge voltage generated by
a thunderbolt. Category I has the lowest durability; category IV has the highest durability.
Category II indicates a power supply whose voltage has been reduced by two or more
levels of isolating transformers from the public power distribution.

9.2.4 Control panel

Because the programmable controller is an open device (a device designed to be stored
within another module), be sure to use it after storing in the control panel.*
(1) Electrical shock prevention
The control panel must be handled as shown below to protect a person who does not
have adequate knowledge of electricity from an electric shock.
Category IV
Figure 9.12 Installation category for power supply module
* : Also, each network remote station needs to be installed inside the control panel.
• Lock the control panel so that only those who are trained and have acquired
enough knowledge of electric facilities can open the control panel.
• The control panel must have a structure which automatically stops the power
supply when the box is opened.
• For electric shock protection, use IP20 or greater control panel.