12
TROUBLESHOOTING
Error
Code
Error Contents and Cause
(SD0)
The received command differs from the
8330
expected value.
Lapse in separated receiving data has
8331
occurred.
The link ID in receiving data is different
8332
from the expected value.
The running No. in receiving data is
8333
different from the expected value.
The CC-Link Safety master station
8334
cannot recognize the received data.
Safety communication target station
detection error (Error information is
8400
received from a safety communication
target station on CC-Link IE Field
Network.)
*3
This applies when the serial number (first five digits) of the CPU module is "13042" or later.
Corrective Action
• Check the cable status visually or by
a line test.
• Hardware error of the CC-Link Safety
master module or the relevant CC-
Link Safety remote module (Please
consult your local Mitsubishi
representative.)
• Check if the link ID setting of the
relevant remote station and the link
ID that has been set in the network
parameter are identical.
• Hardware error of the CC-Link Safety
master module or the relevant CC-
Link Safety remote module (Please
consult your local Mitsubishi
representative.)
• Check if the setting value of the
Safety refresh monitoring time is
appropriate.
• Hardware error of the CC-Link Safety
master module or the relevant CC-
Link Safety remote module (Please
consult your local Mitsubishi
representative.)
• Check the cable status visually or by
a line test.
• Hardware error of the CC-Link Safety
master module or the relevant CC-
Link Safety remote module (Please
consult your local Mitsubishi
representative.)
Check the error code of the
communication target station on CC-
Link IE Field Network.
12.3 Error Code List
12.3.8 Error code list (8000 to 9000)
9
Corresponding
CPU
QS
10
QS
11
QS
12
QS
QS
*3
QS
12
- 58