TROUBLESHOOTING
Error code
Error item
(Hexadecimal)
41CB
H
41CC
H
41CD
H
41CE
H
41CF
H
41D0
H
41D1
H
41D5
H
41D8
H
41E1
H
File-related
41E9
H
errors
41EC
H
41ED
H
41F2
H
41FA
H
41FB
H
41FC
H
41FD
H
12
- 73
12.5 Error codes returned to request source during communication with CPU module
Table12.10 Error code (Continue)
Error details
The file name is specified in a wrong method.
The specified file does not exist.
Access to the file is inhibited by the system.
The specified file is write-disabled since its
attribute is read-only.
The specified drive (memory) capacity was
exceeded.
The specified drive (memory) has no free
space.
The file name is specified in a wrong method.
The file of the same name exists.
The specified file is being accessed.
Access to the flash ROM was unsuccessful.
The specified file is being accessed.
The file system of the specified drive
(memory) is logically corrupted.
The specified drive (memory) does not have
continuous free space.
(The free space for file is sufficient but the
continuous free space is insufficient.)
Operation cannot be performed since the
specified drive (memory) is Flash ROM.
Program was written beyond the area where
the program can be executed.
Operation is being performed for the file
already specified for the same peripheral
device.
An attempt was made to erase the drive
(memory) being used.
There are no data written to the Flash ROM.
Corrective action
Execute again after checking the file name.
Execute again after checking the file.
Do not access the specified file.
The specified file is write-inhibited. Execute again after
checking the attribute.
Execute again after checking the drive (memory)
capacity.
Execute again after increasing the free space of the drive
(memory).
Execute again after checking the file name.
If the error recurs after re-execution, the file information
data may be corrupted.
After backing up the data in the CPU module, execute
PLC memory format.
Forcibly execute the request, or execute after changing
the file name.
Execute again after a while.
• After backing up the data, execute write to PLC (Flash
ROM).
Execute again after some time.
The file information data may have been corrupted.
After backing up the data in the CPU module, execute
PLC memory format.
Execute again after deleting unnecessary files or
executing PLC memory arrangement.
Execute again after checking the specified drive
(memory).
When performing operation for the Flash ROM, use write
to PLC (Flash ROM).
Execute again after reducing either the already written
program or newly written program.
Execute again after the currently performed operation is
completed.
The specified drive (memory) is being used and cannot
be erased.
Write a file by executing write to PLC (Flash ROM).