Installing the Chassis in a Rack

Installing the Chassis in a Rack

Rack-Mounting the Chassis

The 7705 SAR-M chassis is designed for installation in a 19-inch rack. The rack-mount
brackets are factory-installed.
Table 14
European customers can order adapter brackets to allow mounting of the 7705 SAR-M
chassis (actively cooled variants only) in an ETSI rack. Contact your Alcatel-Lucent sales
representative to order the ETSI adapter bracket kit (part number 3HE05260AA).
86
Danger: Only trained and qualified personnel should install or replace this equipment.
Warning:
Always wear an ESD-preventive wrist or ankle strap and always connect an ESD strap
to a nearby ground point that is connected to the site grounding point when working on
the 7705 SAR-M. Typical ground points include a properly grounded rack or work
bench.
Failure to comply with the location requirements outlined in
Chassis Location Requirements
equipment failure due to overheating.
Non-conductive coatings (such as lacquer and enamel) must be removed from threads
and other contact surfaces to ensure electrical conductivity. Thread-forming screws with
paint piercing washers may be used for this purpose during installation.
When rack-mounting the chassis in an equipment rack, do not stack one 7705 SAR-M
chassis or any other equipment directly on top of another 7705 SAR-M chassis, such
that the bottom chassis is supporting other devices. Each chassis must be secured in
the rack with the appropriate mounting apparatus.
lists the rack-mounting components.
may impede proper airflow, which may result in
Figure 18
illustrates the installation of the chassis in a rack.
7705 SAR-M Chassis Installation Guide