Chimney Termination Requirements; 2-10-03 Rule - Quadra-Fire 31M-ACC-MBK Owner's Manual

3100 wood stove series
Hide thumbs Also See for 31M-ACC-MBK:
Table of Contents

Advertisement

R
D. Chimney Termination Requirements
Follow manufacturers instructions for clearance, securing,
fl ashing and terminating the chimney.
Must have an approved and listed cap
Must not be located where it will become plugged by
snow or other material
Must terminate at least 3 feet (91cm) above the roof
and at least 2 feet (61cm) above any portion of the
roof within 10 feet (305cm).
Must be located away from trees or other struc-
tures
E. 2-10-3 Rule
These are safety requirements and are not meant to assure proper fl ue draft.
Figure 19.1
Figure 19.2
July 7, 2011
NOTE:
Chimney performance may vary.
Trees, buildings, roof lines and wind conditions affect
performance.
Chimney height may need adjustment if smoking or
overdraft occurs.
7033-277I
3100 Wood Stove Series (ACC)
Page 19