Integrated Control Diagnostic Modes; Diagnostic Push Button; Error Code Recall Mode; Program Unit Capacity/Size Mode - Lennox EL296DF045XV36B Unit Information

Icomfort - enabled el296dfv(x) series units
Hide thumbs Also See for EL296DF045XV36B:
Table of Contents

Advertisement

Display
No change (idle)*
Solid "E"
Solid "F"
Solid "P" (variable speed only)
__
Two horizontal bars __
* No change implies the display will continue to show whatever is currently being displayed for normal operation (blinking
decimal, active error code, heat state, etc..)
Diagnostic LED (Figure 4)
The seven-segment diagnostic LED displays operating
status, target airflow, error codes and other information.
The table beginning on Page 10 lists diagnostic LED
codes.
Diagnostic Push Button (Figure 4)
The diagnostic push button is located adjacent to the
seven-segment diagnostic LED. This button is used to en­
able the Error Code Recall "E" mode, the Flame Signal "F"
mode and "P" the Program Unit Capacity/Size mode. Press
the button and hold it to cycle through a menu of options.
Every five seconds a new menu item will be displayed.
When the button is released, the displayed item will be se­
lected. Once all items in the menu have been displayed, the
menu resumes from the beginning until the button is re­
leased.

Error Code Recall Mode

Select "E" from the menu to access the most recent 10 error
codes. Select "c" from the Error Code Recall menu to clear
all error codes. Button must be pressed a second time
while "c" is flashing to confirm command to delete codes.
Press the button until a solid "≡" is displayed to exit the Error
Code Recall mode.
Flame Signal Mode
Select "F" from the menu to access the flame signal mode.
The integrated control will display the flame current on
seven-segment LED in in micro amps (uA).
Flame signal mode is exited after any of the following:
D Power is reset
D Pressing and holding push button until 3 horizontal
lines "≡" are displayed
D 10 minutes after entering the flame sense mode.
TABLE 4

Integrated Control Diagnostic Modes

Action (when button released)
Remain in idle mode
Enter diagnostic recall mode
Enter flame signal mode
Program unit capacity/size (Unit Code)
Soft disable

Program Unit Capacity/Size Mode

After the "P" is selected (by releasing the push button) the
integrated control will start flashing the "P" on display for 90
seconds. If push button is pressed again and held during
that time, the control will start to display characters corre­
sponding to different variable speed furnace models for 3
seconds each. While the wanted character-model is dis­
played push button has to be released. Selected option will
flash display for 10 seconds and during that time push but­
ton has to be pressed and held for 5 seconds. Once control
accepts new setting it will store data in non-volatile memory
and reset itself. If 10 seconds expires or push button is held
less than 5 seconds, control will exit field test mode and go
into idle without changing programming the unit size.
Soft Disable
Soft disabling is when thermostat finds a device on the BUS
that it does not recognize and the thermostat sends a the
device a message to be in soft disabling mode until proper­
ly configured. Two horizontal bars will display.
Steps to follow if the damper control module is displaying
the soft disable code.
Page 9
1- Confirm proper wiring between all devices (thermo­
stat, damper control module, indoor and outdoor).
2- Cycle power to the control that is displaying the soft
disable code.
3- Put the room thermostat through set up.
4- Go to setup / system devices / thermostat / edit /
then push reset.
5- Go to setup / system devices / thermostat / edit /
then push resetAll.