II-PLACEMENT AND INSTALLATION
Pipe & Fittings Specifications
All pipe, fittings, primer and solvent cement must conform
with American National Standard Institute and the Ameri
can Society for Testing and Materials (ANSI/ASTM) stan
dards. The solvent shall be free flowing and contain no
lumps, undissolved particles or any foreign matter that ad
versely affects the joint strength or chemical resistance of
the cement. The cement shall show no gelation, stratifica
tion, or separation that cannot be removed by stirring. Re
fer to the table 18 below for approved piping and fitting ma
terials.
CAUTION
Solvent cements for plastic pipe are flammable liq
uids and should be kept away from all sources of
ignition. Do not use excessive amounts of solvent
cement when making joints. Good ventilation should
be maintained to reduce fire hazard and to minimize
breathing of solvent vapors. Avoid contact of ce
ment with skin and eyes.
TABLE 18
PIPING AND FITTINGS SPECIFICATIONS
Schedule 40 PVC (Pipe)
Schedule 40 PVC (Cellular Core Pipe)
Schedule 40 PVC (Fittings)
Schedule 40 CPVC (Pipe)
Schedule 40 CPVC (Fittings)
SDR-21 PVC or SDR-26 PVC (Pipe)
SDR-21 CPVC or SDR-26 CPVC (Pipe)
Schedule 40 ABS Cellular Core DWV (Pipe)
Schedule 40 ABS (Pipe)
Schedule 40 ABS (Fittings)
ABS-DWV (Drain Waste & Vent)
(Pipe & Fittings)
PVC-DWV (Drain Waste & Vent)
Pipe & Fittings)
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer
PVC Solvent Cement
CPVC Solvent Cement
ABS Solvent Cement
PVC/CPVC/ABS All Purpose Cement For
Fittings & Pipe of the same material
ABS to PVC or CPVC Transition Solvent
Cement
CANADA PIPE & FITTING & SOLVENT
CEMENT
PVC & CPVC Pipe and Fittings
PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition Cement
POLYPROPYLENE VENTING SYSTEM
®
PolyPro
by Duravent
®
InnoFlue
by Centrotherm
EL296DFV exhaust and intake connections are made
of PVC. Use PVC primer and solvent cement when
using PVC vent pipe. When using ABS vent pipe, use
transitional solvent cement to make connections to
the PVC fittings in the unit.
Use PVC primer and solvent cement or ABS solvent cement
meeting ASTM specifications, refer to Table 18. As an alter
nate, use all purpose cement, to bond ABS, PVC, or CPVC
pipe when using fittings and pipe made of the same materi
als. Use transition solvent cement when bonding ABS to ei
ther PVC or CPVC.
Low temperature solvent cement is recommended during
cooler weather. Metal or plastic strapping may be used for
vent pipe hangers. Uniformly apply a liberal coat of PVC
primer for PVC or use a clean dry cloth for ABS to clean in
side socket surface of fitting and male end of pipe to depth
of fitting socket.
Canadian Applications Only - Pipe, fittings, primer
and solvent cement used to vent (exhaust) this ap
pliance must be certified to ULC S636 and supplied by a
single manufacturer as part of an approved vent (ex
haust) system. In addition, the first three feet of vent
pipe from the furnace flue collar must be accessible for
inspection.
Venting Options
D1785
The EL296DFV is shipped with vent exhaust / air intake
F891
connection at the top cap. See figure 17. Using parts pro
D2466
vided, the furnace may be field modified to have these
F441
connections on the right side of the furnace cabinet. See
F438
figure 19 and follow the steps below. For left side venting
D2241
order kit 87W73.
F442
1 - Remove inner blower door.
F628
2 - Loosen hose clamps which attach rubber fittings to the
D1527
D2468
D2661
3 - Loosen the clamp which secures the pipes at the blow
D2665
4 - Remove white PVC pipes, slide up and out thru the top
ASTM
SPECIFICATION
F656
5 - Remove the black plastic fitting in top cap which pre
D2564
F493
6 - Remove the remaining parts of the pipe clamp at the
D2235
D2564, D2235, F493
7 - Remove the sheet metal patch plate on the side of the
D3138
MARKING
8 - Re-use the patch plate to cover the hole in the top cap.
ULCS636
ULC-S636
ULC-S636
ULC-S636
Page 31
IMPORTANT
white PVC pipes inside the vestibule area. See figure
17.
er deck. See figure 17.
cap.
viously aligned the PVC pipes.
blower deck.
cabinet which covers the openings for side venting op
tion. Save screws for reuse.
See figure 18. Remove the 2 screws which secure the
top cap to the furnace on the right side and re-install
securing the right edge of the patch plate and the right
side of the top cap to the furnace. Use 2 self-drilling
sheet metal screws (provided) to finish securing the
left edge of the patch plate on the left side.