NOTE- To obtain accurate reading, shut off all other gas
appliances connected to meter.
TABLE 25
GAS METER CLOCKING CHART
Seconds for One Revolution
Natural
EL296
Unit
1 cu ft
Dial
-045
80
-70
55
-90
41
-110
33
-135
27
Natural-1000 btu/cu ft
IMPORTANT
For safety, shut unit off and remove manometer as
soon as an accurate reading has been obtained.
Take care to replace pressure tap plug.
G- Proper Combustion
LP/Propane Conversion Kit and Pressure Switch Requirements at Varying Altitudes
Natural to
LP/Propane
EL296
Unit
0 - 7500 ft
(0 - 2286m)
-045
-070
*11K51
-090
-110
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1370 m).
EL296
Unit
All Sizes
NOTE -
A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion
procedure.
LP
2 cu ft
1 cu ft
2 cu ft
Dial
Dial
DIAL
160
200
400
110
136
272
82
102
204
66
82
164
54
68
136
LP-2500 btu/cu ft
High Altitude
Natural Burner
Orifice Kit
7501 - 10,000 ft
(2286 - 3038m)
73W37
Manifold Pressure Settings
Manifold Pressure in.wg.
Gas
Low Fire
Natural
1.7
LP/propane
4.9
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking com
bustion. See sections E- and F-. Take combustion sample
beyond the flue outlet. Table 26 shows acceptable com
bustions. The maximum carbon monoxide reading should
not exceed 100 ppm.
CO
EL296
Unit
Low Fire
045
5.6 - 6.6
070
5.5 - 6.5
090
5.9 - 6.9
110
6.3 - 7.3
The maximum carbon monoxide reading should not exceed 100ppm.
H- High Altitude
The manifold pressure, gas orifice and pressure switch
may require adjustment or replacement to ensure proper
operation at higher altitudes. See table 27 for gas conver
sion and pressure switch kits. See table 28 for manifold
pressures
TABLE 27
High Altitude
LP/Propane Burner
Orifice Kit
7501 - 10,000 ft
(2286 - 3038m)
*11K46
TABLE 28
High Fire
3.5
10.0
Page 57
TABLE 26
%
CO
%
2
For Nat
2
High Fire
Low Fire
7.8 - 8.8
6.6 - 7.6
7.3 - 8.3
6.5 - 7.5
7.8 - 8.8
6.9 - 7.9
8.2 - 9.2
7.3 - 8.3
High Altitude Pressure Switch
4501 - 7500 ft
7501 -10,000 ft
(1373 - 2286m)
(2286 - 3048m)
14A57
14A50
14A55
14A56
14A54
14A53
14A46
14A51
Supply Line Pressure in. w.g.
Min
4.5
11.0
For L.P
High Fire
9.1 - 10.1
8.6 - 9.6
9.1 - 10.1
9.5 - 10.5
Max
10.5
13.0