proved during the 4-second period, the control will try four
more times with an inter purge and warm-up time between
trials of 35 seconds. After a total of five trials for ignition (in­
cluding the initial trial), the control goes into Watchguard-
Flame Failure mode. After a 60-minute reset period, the
control will begin the ignition sequence again.
Two Stage Operation / Thermostat Selection DIP
Switch
The control can be utilized in two modes: SINGLE-STAGE
thermostat or TWO-STAGE thermostat. The thermostat
selection is made using a DIP switch and must be posi­
tioned for the particular application. DIP switch 1, labeled
T"STAT HEAT STAGE is factory-set in the OFF position for
use with a two-stage thermostat. Move the DIP switch to
ON for use with a single stage thermostat.
While in the single-stage thermostat mode, the burners will
always fire on first-stage heat. The combustion air inducer
will operate on low speed and indoor blower will operate on
low heat speed. The unit will switch to second stage heat
after a "recognition period". DIP switch 2, labeled SECOND
STAGE DELAY, is factory set in the OFF position for a 7
minute recognition period. The switch can be moved to the
ON position for a 12 minute recognition period, after which
time the unit will switch to second­stage heat. While in the
two-stage thermostat mode, the burners will fire on first-
stage heat. The combustion air inducer will operate on low
speed and indoor blower will operate on low heat speed.
The unit will switch to second-stage heat on call from the
indoor thermostat. If there is a simultaneous call for first
and second stage heat, the unit will fire an first stage heat
and switch to second stage heat after 30 seconds of opera­
tion. See Sequence of Operation flow charts in the back of
this manual for more detail.
®
SureLight
Control 5 Pin Terminal Designation
PIN #
1
2
3
4
5
®
SureLight
Control 12 Pin Terminal Designation
PIN #
1
2
3
4
5
6
7
8
9
10
11
12
®
SureLight
Control 6 Pin Terminal Designation
PIN #
1
2
3
4
5
6
Page 6
TABLE 1
Function
Ignitor
Combustion Air Inducer High Speed
Combustion Air Inducer Low Speed
Combustion Air Inducer Neutral
Ignitor Neutral
TABLE 2
Function
Gas Valve Second Stage
Second Stage Prove Switch
Rollout Switch In
Ground
24V Hot
Primary Limit In
Gas Valve First Stage
Gas Valve Common
24V Neutral
Ground
Rollout Switch Out
First Stage Prove Switch
TABLE 3
Function
Data Input From Motor
Common
Not Used
Data Output To Motor
5 Volt Bias Supply
Not Used