Profibus Slave Unit; Specifications - Omron CJ1W-PRT21 Operation Manual

Machine automation controller, cj / nj-series, profibus slave unit, cpu unit
Hide thumbs Also See for CJ1W-PRT21:
Table of Contents

Advertisement

1 Features and System Configuration
1-3

PROFIBUS Slave Unit

1-3-1

Specifications

Model Code
Maximum number of Units per
CPU system
Current consumption
Weight
Storage temperature
Operating temperature
Operating humidity
Conformance to EMC- and
environmental standards
Switch settings
Indicators
No. of CIO words allocated
No. of DM words allocated
Amount of I/O data per Unit
1-14
40
400 mA (maximum) at 5 VDC from CPU power supply
90 g (typical)
o
o
-20
C to +70
C
o
o
0
C to +55
C
10 to 90% (non-condensing)
EN50081-2
EN61131-2
Special I/O Machine number (00-95) by 2 rotary switch
PROFIBUS-DP node address (00-99) by 2 rotary switches
Unit status: RUN (green indicator), ERC (red indicator)
Network status: COMM (green indicator), BF (red indicator)
CPU status: ERH (red indicator)
CPU -> Unit: 1 word control data
Unit -> CPU: 1 word status data
Unit -> CPU: 8 words of Unit setup information
Fixed:
2 words CIO area (one in, one out) for Unit status + Software Switches.
1 word status information from the host CPU, containing operation status
and (see 3-8 CPU Status Information). This information will be sent to the
PROFIBUS master:
• as extended diagnostics, only at a change of data content.
• optionally, attached to the I/O data, each PROFIBUS cycle.
Variable:
2 user-defined areas for PROFIBUS I/O data, with the following restric-
tions:
• Up to 100 words input in one CPU area (CIO, H, D, EM).
• Up to 100 words output in one CPU area (CIO, H, D, EM).
• Inputs+outputs must be 180 words or less
CJ-series PROFIBUS Slave Unit Operation Manual for NJ-series CPU Unit (W510)
CJ1W-PRT21

Advertisement