Omron CJ1W-PRT21 Operation Manual page 88

Machine automation controller, cj / nj-series, profibus slave unit, cpu unit
Hide thumbs Also See for CJ1W-PRT21:
Table of Contents

Advertisement

3 Data Exchange with the CPU Unit
3-7
Device Variables for CJ-series Unit
(Configuration)
The CJ1W-PRT21 provides 8 consecutive DM words to indicate configuration and parameterisation
data received from the PROFIBUS-DP master unit. These words are not part of the cyclic refresh, but
the unit writes this information to the Host CPU when the data in the unit changes. At power-on, or at a
reset of the unit, all data will be set to 0. The DM words are in the area assigned to the Special I/O unit,
depending on the Machine No (see section 3-5-1 Data Flow).
Name of Device Variable for CJ-
series Unit
*_SlvParamSta
*_SlvMstrAdr
*_SlvGrp1
*_SlvGrp2
*_SlvGrp3
*_SlvGrp4
*_SlvGrp5
*_SlvGrp6
*_SlvGrp7
*_SlvGrp8
*_SlvWdtFact1
*_SlvWdtFact2
*_SlvOutSta
*_SlvOutAreaCode
*_SlvOutHoldBusErr
*_SlvOutIntelMd
*_SlvOutStartAdr
*_SlvOutDatLen
*_SlvInSta
*_SlvInAreaCode
*_SlvInProgCont
*_SlvInProgExit
*_SlvInFatlCont
*_SlvInFatlExit
*_SlvInIntelMd
*_SlvInclPLCSta
*_SlvInStartAdr
*_SlvInDatLen
3-20
Type
R/W
DWORD
R
Slave parameter data (see section 3-7-1)
USINT
R
Bits 00-07: Master address
BOOL
R
Bit 08: Slave assigned to Group 1
BOOL
R
Bit 09: Slave assigned to Group 2
BOOL
R
Bit 10: Slave assigned to Group 3
BOOL
R
Bit 11: Slave assigned to Group 4
BOOL
R
Bit 12: Slave assigned to Group 5
BOOL
R
Bit 13: Slave assigned to Group 6
BOOL
R
Bit 14: Slave assigned to Group 7
BOOL
R
Bit 15: Slave assigned to Group 8
USINT
R
Bits 00 to 07: Watchdog factor 1
USINT
R
Bits 08 to 15: Watchdog factor 2
LWORD
R
Slave Output Data (see section 3-7-2)
USINT
R
Bits 00 to 07: Output area code
BOOL
R
Bit 08: Data hold on PROFIBUS fail
BOOL
R
Bit 12: Outputs Intel mode
UINT
R
Output start address
UINT
R
Output data length
LWORD
R
Slave Input Settings (see section 3-7-3)
USINT
R
Bits 00 to 07: Input area code
BOOL
R
Bit 08: Continue in PROGRAM mode
BOOL
R
Bit 09: Exit in PROGRAM mode
BOOL
R
Bit 10: Continue on fatal error
BOOL
R
Bit 11: Exit on fatal error
BOOL
R
Bit 12: Inputs Intel mode
BOOL
R
Bit 15: Include PLC status in input data
UINT
R
Input start address
UINT
R
Input data length
CJ-series PROFIBUS Slave Unit Operation Manual for NJ-series CPU Unit (W510)