Omron CJ1W-PRT21 Operation Manual page 103

Machine automation controller, cj / nj-series, profibus slave unit, cpu unit
Hide thumbs Also See for CJ1W-PRT21:
Table of Contents

Advertisement

Event code
Event name
38180000 hex
Parame-
ter/Configu-
ration Error
CJ-series PROFIBUS Slave Unit Operation Manual for NJ-series CPU Unit (W510)
Meaning
The Slave has
Parameter Error can be caused by:
received incorrect
• Invalid standard parameter settings (valid
parameter and/or
settings are described in the PROFIBUS
configuration mes-
standard).
sages from a Mas-
• Invalid user parameter settings (allowed
ter Unit.
settings are described in the GSD file of
the Unit).
• Incorrect start addresses for I/O data in
the host CPU system. If one of them is
invalid, parameter error is indicated, plus
*_StartAdrInErr and/or *_StartAdrOutErr
will be set.
Configuration Error can be caused by:
• Input - or output length > 100 words
• Input + output length > 180 words
• Input length < 2 words while CPU status
should be included.
• Input - or output length causing errors
indicated by *_EndAdrInErr,
*_EndAdrOutErr
4 Troubleshooting and Maintenance
Assumed cause
Level
Maj
Prt
Min
Obs Info
X