Parameterization by the PROFIBUS
Master Unit
The parameterisation of the passive stations by the master is first done in the start-up phase of the
PROFIBUS-DP system and is also possible in the data exchange mode. The first 10 bytes of parameter
data are defined by the PROFIBUS standard the additional 9 bytes are device specific. The format of
the parameters is depicted in the following table.
Byte
7
0
Lock
Req
1
2
3
4
5
6
7
0
8
0
9
0
10
0
11
12
13
14
Incl. Sta-
tus
15
16
17
Although the Unit does not support PROFIBUS-DP/V1 functionality, the three DPV1 status bytes are
reserved in the Set_Prm message. Only the 2 indicated bits can be set by the user.
A-14
Bit Position
6
5
4
Unlock
Sync
Freeze
Req
Req
Req
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
Fail
0
0
Safe
0
0
0
0
0
0
0
0
Motor-
ola/
Intel
codes to indicate CIO, H, W, D, E0 to EC
00 to 7F
00 to FF
0
0
Motor-
ola/
Intel
codes to indicate CIO, H, W, D, E0-EC
00 to 7F
00 to FF
CJ-series PROFIBUS Slave Unit Operation Manual for NJ-series CPU Unit (W510)
3
2
1
WD on
Res
Res
0
WD
0
1 ms
0
0
0
0
0
0
0
0
0
Action Fatal Error
Action PRGmode
(Continue/Stop)
(Continue/Stop)
Designation
0
Res
Station status
WD_Fact_1
WD_Fact_2
MinTSDR
Ident_Number_High
Ident_Number_Low
Group_Ident
0
DPV1_Status_1
0
DPV1_Status_2
0
DPV1_Status_3
Reset/
Output options*
Hold
Output Area*
Out start address High*
Out start address Low*
Input options*
Input Area*
In start address High*
In start address Low*