OPERATING PROCEDURE
4. Removing the compressor.
(1) Remove the cabinet. (Refer to 1.)
(2) Remove the terminal cover.
(3) Pull out lead from the compressor terminal, then remove
the thermal protector.
(4) Remove the suction pipe welded section and discharge
pipe welded section using a burner.
Pull out when the welding melts.
(5) Remove the sound proof felt.
(6) Remove the compressor 3 set nuts.
(7) Remove the compressor.
Note
:
Before using the welder, confirm that the pressure gauge is
0 kg/cm
2
.
When using the welder, leave the service port open and release
the pressure to avoid expansion by heat.
Photo 5
Discharge
pipe
155
PHOTOS
Sound proof felt
Suction
pipe