These instructions include the Benchmark Commissioning Checklist and should be left with the user for safe keeping. They must be read in conjunction with the Flue Installation
Summary of Contents for Baxi EcoBlue Advance 13 Heat ErP
Page 1
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... 7219719 - 01 (04/15) United Kingdom EcoBlue Advance Heat 13 - 16 - 19 - 25 - 30 Gas Fired Wall Mounted Condensing Boiler Installation and Service Manual These instructions include the Benchmark Commissioning Checklist and should be left with the user for safe keeping.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... 7.5.1 Check the Operational (Working) Gas Inlet Pressure & Gas Rate 7.6 Final Instructions 8 Operation 8.1 General 8.2 Start-Up 8.3 Shutdown 8.4 Use of the Control Panel 8.5 Frost Protection...
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... 1.2 Additional Documentation These Installation & Service Instructions must be read in conjunction with the Flue Accessories & Fitting Guide supplied in the Literature Pack. Various timers, external controls, flue accessories, etc. are available as optional extras. Full details are contained in the relevant sales literature.
Baxi Heating Uk Limited being the manufacturer / distributor within the European Economic Area of the following Baxi EcoBlue Advance Heat ErP declare that the above is in conformity with the provisions of the Council Directive 2009/142 EC 92/42 EEC 2004/108 EC 2006/95 EC...
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... page 11 2 Safety 2.1 General Safety Instructions DANGER If you smell gas: 1. Turn off the gas supply at the meter 2. Open windows and doors in the hazardous area 3.
Page 9
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Heat Output Pn (Non Condensing 70° C Mean Water Temp) 13 model 16 model 19 model 25 model 30 model Max Gas Rate (Natural Gas - G20)
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... NOTE: All data in this section are nominal values and subject to normal production tolerances. Product Characteristics Database (SEDBUK) SAP 2009 Annual Efficiency 13 model - 89.2% 25 model - 89.1%...
Page 11
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... DIMENSIONS A 625mm A2 25mm B 270mm C 370mm D 116mm Ø Min. E 165mm F 155mm G 110mm H 550mm For clearances see Section 5.3.6 NOTE: There must be no part of the air duct (white tube) visible outside the property after installation.
17 4 Description of the Product 4.1 General Description The Baxi EcoBlue Advance Heat Range are gas fired wall mounted powered flue condensing boilers. The maximum output of the boiler is :- 13 model - 13 kW 12 of 55...
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... 16 model - 16 kW 19 model - 19 kW 25 model - 25 kW 30 model - 30 kW The boiler modulates automatically to the system load up to the set output. It is designed for use on Natural Gas (G20) only.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Switched Live On: When the boiler switched live turns on the boiler, a 20 second check cycle takes place. If the flow temperature is less than the boiler set-point temperature the ignition cycle will start.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... The temperature on this rotary knob must be set to a higher temperature than the cylinder thermostat to achieve the required hot water demand. 4.5 Standard Delivery...
Complete the label supplied with the inhibitor and attach to the inside of the boiler case. Detail of system treatment should be added for future reference. For information or advice regarding any of the above contact Baxi Customer Support 0344 871 1525.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Fig. 5 If Conditions Require, This System Possible Fig. 6 Alternative Low Head Installation Venting A method of venting the system during filling and commissioning is provided by an automatic air vent fitted inside the boiler. The air vent is supplied in the open position.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Method of determining minimum valve of expansion vessel volume for sealed systems using Baxi Boilers Static Head Vessel Charge Pressure Initial System Pressure Multiply Total Water (Bar)
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Fig. A In GB Only Fig. B In GB Only 5.3.4 Ventilation Where the appliance is installed in a cupboard or compartment, no air vents are required.
Page 21
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... *It is NOT RECOMMENDED to connect upstream of the sink or other waste water receptacle ! page 27 21 of 55 23/01/2018, 11:44...
Page 22
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... If the boiler is fitted in an unheated location the entire condensate discharge pipe should be treated as an external run and sized and insulated accordingly. In all cases discharge pipe must be installed to aid disposal of the condensate. To reduce the risk of condensate being trapped, as few bends and fittings as possible should be used and any burrs on cut pipe removed.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Fig. 9 Fig. 10 5.3.6 Clearances - Access in Service A flat vertical area is required for the installation of the boiler. These dimensions include the necessary clearances around the boiler for case removal, spanner access and air movement (Figs.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... 5.3.7 Flue/Chimney Location The following guidelines indicate the general requirements for siting balanced flue terminals. For GB recommendations are given in BS 5440 Pt 1. For IE recommendations are given in the current edition of I.S. 813 "Domestic Gas Installations".
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Fig. 12 If fitting a Plume Displacement Flue Kit, the air inlet must be a minimum of 150mm from any opening windows or doors (Fig. 13). Fig. 13 page 31 5.3.8 Horizontal Flue/Chimney Systems...
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Fig. 14 page 32 5.3.9 Flue/Chimney Trim The flexible flue trims supplied can be fitted on the outer and inner faces of the wall of installation (Fig.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... 5.3.10 Terminal Guard When codes of practice dictate the use of terminal guards (Fig. 15) "Multifit" accessory part no. 720627901 can be used (NOTE: This is not compatible with Flue Deflector referred too below).
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Fig. 18 5.4.2 Initial Preparation After considering the site requirements, position the fixing template on the wall ensuring it is level both horizontally and vertically (Fig. 20).
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Fig.22 page 34 5.4.3 Making the Water Connections (Fig. There are two water connections at the top of the boiler. The left connection is the return pipe (indicated with blue label) and the flow the right hand one (indicated with red label).
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Fig. 23 5.4.6 Connecting the Gas Supply The elbow and nut assembly supplied must be used to connect to the gas supply. The flared end of the elbow is 22mm O.D.
Page 31
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Fig. 24 Fig. 25 Fig. 26 Fig. 27 page 36 Remove the boiler blank adaptor and replace with the boiler adaptor ensuring that the gasket is in position. Replace the gasket if necessary (Fig.
Page 32
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Make good between the wall and air duct outside the building, appropriate to the wall construction and fire rating. If necessary fit a terminal guard (see Section 5.3.11).
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... 6.1.2 Connecting the "In Case" Rear Flue Internal Fitting Kit part no. 7215374 is available for the "In Case" Rear Flue. It can be used where access to "make good" outside is difficult or not possible e.g. blocks of flats.
Page 34
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Fig. 35a Fig. 36 page 38 Undo the screws securing the rear flue blanking plate. Firmly grip the central spigot and pull the plate off the boiler. Ensure that the flue connection seals remain in place (Fig.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Fig. 38 page 39 6.2 Electrical Connections 6.2.1 Electrical Connections of the appliance Section 5.2.2. for details of the electrical supply. 1.3 metres of 3 core cable and a multipin male plug connected to a female socket at the left rear are supplied with the boiler.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Key to colours Blue br - Brown White Orange gr - Grey g/y - Green/Yellow page 40 6.3 Filling the System Section 5.2.6. for details of treating the system, Section 5.2.7.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Before turning on the electrical and gas supply to commission the boiler, check that all the installation requirements for the chosen heating system and flue options have been satisfied.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Follow the flow chart opposite. page 44 7.5 Configuring the System 7.5.1 Check the Operational (Working) Gas Inlet Pressure Ensure that all controls are calling for heat and maximum load is applied to the system.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... With any other appliances & pilot lights turned OFF the gas rate can be measured. It should be as shown in Section 3.1 Technical Data. For IE, it is necessary to complete a "Declaration of Conformity" to indicate compliance with I.S. 813. An example of this is given in I.S. 813 "Domestic Gas Installations".
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... page 46 8 Operation 8.1 General It is the responsibility of the installer to instruct the user in the day to day operation of the boiler and controls and to hand over the completed Benchmark Checklist at the back of this manual.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... The integrity of the boiler combustion circuit and relevant seals. The operational gas inlet pressure and the gas rate as described in Section 7.5.1. The combustion performance as described in "Check the Combustion Performance" below.
Page 42
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Fig. 43 Unscrew the two screws located on the lower front panel (Fig. 43). Slide the lower front panel forward and hinge down or remove (Fig. 44).
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... page 51 10.3 Specific Maintenance Operation WARNING When changing components ensure that both the gas and electrical supplies to the boiler are isolated before any work is started.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Fig. 48 page 52 Removal of the fan air duct and flue outlet duct is necessary to enable the changing of the pressure switch, flow temperature sensor, return temperature sensor, overheat sensor and gas valve.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Fig. 49 & Fig. 50 page 53 10.3.6 Flow Temperature Sensor (Fig. The sensor is fitted in a 'dry' pocket. Disconnect the wiring from the flow temperature sensor.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... 10.3.8 Return Temperature Sensor (Fig. The sensor is fitted in a 'dry' pocket. Disconnect the wiring from the return temperature sensor. Unscrew the sensor from the top of the heat exchanger.
Page 47
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... operated by a competent person - see section 10.1.3. A T25 Torx screwdriver will be required. Ensure that the gas supply to the boiler is isolated. Remove the ducts as described in Section 10.3.4...
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... If the boiler will not light, prior to final setting, use a suitable hexagon key to wind out the Throttle Adjustment Screw until it is flush with the valve body, then turn the screw 4 full turns clockwise.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Fig. 59 10.3.12 User Interaction Controller (Fig. Disconnect the User Interaction Controller cable from the PCB and undo the cable gland locknut. Note the setting and carefully prise off the rotary temperature selection knob.
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... Do not turn either adjustment screw more than 1/8 of a turn at a time. Allow the analyser reading to settle before any further adjustment. Fig. 63 Press the Chimney Sweep button twice to select the minimum rate.
Dismantle the chimney system and remove the boiler from the wall mounting frame. page 60 13 Spare Parts 13.1 General If, following the annual inspection or maintenance any part of the boiler is found to need replacing, use Baxi Spare Parts only. 51 of 55 23/01/2018, 11:44...
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... 13.2 Spare Parts List Key No. Description Manufacturers Part No. Parameter Unit 7216298 Sensor Kit 7216301 Automatic Air Vent 7216300 Ignition/Sensing Electrode 7216299 Pressure Switch 7212522 Combustion Control Unit...
Page 53
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... page 62 SERVICE RECORD It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed. Service Provider Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturers instructions.
Page 54
Baxi EcoBlue Advance 13, 16, 19, 25, 30 Heat ErP Installation Manual http://interpart.partsarena.eu/System/DATA/Dx/DS1/installation/S219/... page 63 Baxi Customer Support 0344 871 1525 Opening hours Monday - Friday, 8.00am-6.00pm Weekends and Bank Holidays, 8.30am-2.00pm Please note calls may be recorded for training and monitoring purposes baxi.co.uk...
Page 55
For the warranty to be maintained, please make sure... Benchmark checklist is completed Warranty is registered with Baxi The boiler has an annual service For full terms and conditions, visit www.baxi.co.uk/terms. Failure to adhere to terms and conditions will void your manufacturers warranty. Baxi Brooks House, Coventry Road,...