About The External Damper Operation - Daikin VAM350J7VEB Installer And User Reference Manual

Heat reclaim ventilation unit
Hide thumbs Also See for VAM350J7VEB:
Table of Contents

Advertisement

Supply Fresh-up
(Excessive outdoor air supply)
Example
a
b
c
a
Portion of fresh-up operation
b
Air exhaust
c
Air supply
d
Heat reclaim ventilation unit (VAM)
e
Normal ventilation fan
f
Portion of exhaust operation
g
Air exhaust
h
Sick room
i
Floor area
If an external fan is connected to J1 and JC, take the following into
account:
▪ Setting 19(29)‑0‑03 MUST be set, otherwise the filter cleaning
indication will be displayed at the wrong time.
▪ Make sure that setting 18(28)‑8 is still set for number 01,
indicating fresh-up.
▪ With setting 18(28)‑7 you can choose if there is exhaust air or
supply air fresh-up and if the user interface indicates that fresh-up
is going on.
▪ The following table describes the unit's operation based on setting
1A‑0 and J1, JC:
Setting
Description of
setting (See
"8.2 List of
settings" on
page 24)
1A‑0‑01
Fresh-up
"OFF" (Factory
setting)
1A‑0‑02
Fresh-up "ON"
The unit's fresh-up operation corresponds with the following fan
operation:
Type
Air supply Fresh-up
Ventilation
Air supply
Exhaust
amount
Weak
High
Low
Strong
Ultra high
High
8.5.3

About the external damper operation

Functions
Intake of outdoor air when the heat reclaim ventilation unit is off can
be prevented if an external damper is incorporated in the system.
The heat reclaim ventilation's main unit printed circuit board
operates the heat reclaim ventilation and provides a signal for the
external damper.
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1 – 2017.08
d
"J1", "JC"
"J1", "JC"
Normal open
Normal closed
Normal
Fresh-up
Fresh-up
Fresh-up
Exhaust Fresh-up
Air supply
Exhaust
Low
High
High
Ultra high
Exhaust Fresh-up
(Excessive exhaust air supply)
g
c
e
h
f
d
a
a
X24A
i
d
a
Air suction/discharge grille
b
External damper (field supply)
c
Inspection hole
d
Switch box
e
Heat insulator
f
Outdoor air (fresh air from outdoors)
g
Exhaust air (exhaust air to outdoors)
h
Round shape hood
i
Printed circuit board
j
Power source
The required setting changes for switchover to X24A output (see
below for details).
Essential wiring
See
"6.5.2 Opening the switch box" on
X24A gives an output when the supply air or exhaust air fan is
running. Put setting 18(28)-3 for number 03 or 04.
8.5.4
About the carbon dioxide sensor
With the CO
(carbon dioxide) sensor installed, you can adjust the
2
ventilation volume in function of measured CO
measured concentration value is compared to programmed trigger
values. Make sure that ventilation mode and air flow rate are set to
automatic.
See
"8.2 List of settings" on page 24
▪ Use setting 19(29)‑9‑05 to give control to the CO
▪ Use setting 19(29)‑7 to shift the trigger values.
▪ Use setting 18(28)‑6 to switch between linear and fixed control.
8 Configuration
d
i
b
c
e
h
HRV
b
j
page 16.
concentration. The
2
for the field setting overview.
sensor.
2
Installer and user reference guide
f
g
35