To Change The Settings With Brc301B61 - Daikin VAM350J7VEB Installer And User Reference Manual

Heat reclaim ventilation unit
Hide thumbs Also See for VAM350J7VEB:
Table of Contents

Advertisement

10 Press the Menu/Enter (b) button and confirm the selection with
Yes.
Field Settings
Save the settings?
Yes
No
Return
Setting
11 After you have completed all the changes, press the Cancel
button (a) twice to return to the normal mode.
8.1.2

To change the settings with BRC301B61

Make sure that the switch box lids on the heat reclaim ventilation unit
are closed.
1 With the unit in normal mode, press the Inspection/Trial button
(a) for more than 4 seconds to enter the local setting mode.
2 Use the Ventilation mode button (up - b) and the Airflow rate
button (down - b) to select a mode number.
Result: The code display is blinking.
3 To configure settings for individual units under group control,
press the Timer setting on/off button (c) and select the number
of the unit that you want to configure.
4 To select the setting switch number, press the top section of the
Timer button (d). To select the setting position number, press
the lower section of the Timer button (e).
5 Press the Program/Cancel button (f) once, to enter the setting.
Result: The code display stops blinking and lights up.
6 Press the Inspection/Trial button (a) to return to normal mode.
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1 – 2017.08
c
f
a
NOTICE
b
Setting 18(28)-11 CANNOT be selected with this user
interface.
a
8 Configuration
c
SETTING
d e
b
Installer and user reference guide
23

Advertisement

Table of Contents
loading

Table of Contents