Extreme bend. Do NOT bend the duct over 90°.
Multi bend
Reduced diameter. Do NOT reduce the duct diameter.
▪ The minimum bend radius for flexible ducts is as follows:
(Øduct/2)×1.5
▪ To prevent air leakage, wind aluminium tape around the section
where the duct joints and the ducts are connected.
▪ Install the opening of the supply air as far as possible from the
opening of the return air.
▪ Use ducts with a diameter that fit the unit model. See the data
book.
▪ Install the two outdoor ducts with down slope (slope ratio of 1 in
50 or more) to prevent entry of rain water. Also provide insulation
for both ducts, to prevent dew formation. (Material: 25  mm thick
glass wool)
▪ If the level of temperature and humidity inside the ceiling is always
high, install ventilation inside the ceiling.
▪ Insulate the duct and the wall electrically when a metal duct has to
penetrate the metal lattice and wire lattice or the metal lining of a
wooden structure wall.
▪ Install the ducts in a manner that the wind CANNOT blow inside
the ducting.
VAM350~1000
Name Plate
a
b
c
a
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1 – 2017.08
VAM1500+VAM2000
6.5
6.5.1
d
d
c
a
Aluminium tape (field supply)
b
Insulation material (field supply)
c
Duct joint (accessories)
d
Slope over 1/50
e
Supply air
f
Return air

Electrical wiring

INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable
legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on the site and all electrical
construction
MUST
comply
legislation.
Precautions when connecting electrical
wiring
DANGER: RISK OF ELECTROCUTION
WARNING
If NOT factory installed, a main switch or other means for
disconnection, having a contact separation in all poles
providing full disconnection under overvoltage category  III
condition, MUST be installed in the fixed wiring.
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring MUST be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do NOT come in contact with the piping and sharp
edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high
frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
Installer and user reference guide
6 Installation