Advertisement

Quick Links

EN
User's Manual
CPS1500PIE
CyberPower Systems, Inc.
K01-0000133-03
Website:
www.cpsww.com

Advertisement

Table of Contents
loading

Summary of Contents for CyberPower CPS1500PIE

  • Page 1 User’s Manual CPS1500PIE CyberPower Systems, Inc. K01-0000133-03 Website: www.cpsww.com...
  • Page 2: Safety And Emc Instructions

    (CPS1500PIE Series) maximum branch circuit over-current protection in accordance with the CE requirement. CPS1500PIE Series include CPS1500PIE, CPS1500PIE-FR, CPS1500PIE-UK and other versions. CAUTION! The building wiring socket outlet (shockproof socket outlet) must be easily accessible and close to the EPS.
  • Page 3 EN62040-1-1 EMI: Conducted Emission: IEC/EN 62040-2…Category C2 Radiated Emission: IEC/EN 62040-2……Category C2 Harmonic Current: IEC/EN61000-3-2 Voltage Fluctuations and Flicker: IEC/EN61000-3-3 EMS: IEC/EN61000-4-2(ESD) IEC/EN61000-4-3(RS) IEC/EN61000-4-4(EFT) IEC/EN61000-4-5(lightning surge) IEC/EN61000-4-6(CS) IEC/EN61000-4-8(Magnetic) IEC/EN61000-2-2 (Immunity to low frequency signals) Copyright © 2014 CyberPower Systems, Inc.
  • Page 4: Installing Your Eps

    Wait 10 seconds. Make sure the circuit breaker is depressed and then turn the EPS on. 6. To maintain optimum battery charge performance, make the EPS plugged into an AC outlet at all times. Enabling the switch provides the bypass for charge only. Copyright © 2014 CyberPower Systems, Inc.
  • Page 5: Basic Operation

    *Note:Maximum battery wiring cable length is 2 meters and the cable O.D. must be 6AWG or greater. 4. DC Circuit Breaker Located on the side of the EPS, the circuit breaker serves to provide overload and fault protection. *Note: It is used as INPUT BATTERY SW as well. Copyright © 2014 CyberPower Systems, Inc.
  • Page 6 High resolution and intelligent LCD display shows all the EPS information with icons and messages. For more information please check the DEFINITIONS FOR ILLUMINATED LCD INDICATORS section. 12. LCD Display Toggle / Selected Switch Users can monitor EPS status and set up functions by using the toggle. Copyright © 2014 CyberPower Systems, Inc.
  • Page 7: Installation Guide

    (Step1) Step 2 Step 3 3. Connect the AC OUTPUT connections (AC plugs or terminal connections). (Step2) 4. Connect the AC power source to AC INPUT (Make sure AC power is off first). (Step3) Copyright © 2014 CyberPower Systems, Inc.
  • Page 8 11. When the external battery needs to be maintained or replaced, remember to turn the machine off. Once off, remove the AC power source and switch off the BATTERY SW. before maintenance or replacing the batteries. When the work is complete, please start from Step 1 to re-install the machine. Copyright © 2014 CyberPower Systems, Inc.
  • Page 9: Definitions For Illuminated Lcd

    8. BATTERY CAPACITY Meter: This meter displays the approximate charge level (in 25% increments) of the EPS's external battery. During a blackout or severe brownout, the EPS will switch to battery power, the ON BAT icon will be illuminated and the charge level will decrease. Copyright © 2014 CyberPower Systems, Inc.
  • Page 10: Eps Status Inquiry And Functions Setup

    Delay Time: The time delays for switching from Battery Mode to Line Mode. The machine will switch from Battery Mode to Line Mode within the preset delay time after the AC power transmission reaches stability. Default 0.0 minutes Choice 0.0, 0.5, 1.0, 1.5, 2.0, 2.5, 3.0, 3.5, 4.0 minutes Copyright © 2014 CyberPower Systems, Inc.
  • Page 11 Firmware Version: This function shows the version of the used firmware. Error Code: This function shows the latest record of error codes, if any. Note: For more information about error codes, please see the table on page 14. Copyright © 2014 CyberPower Systems, Inc.
  • Page 12 DO NOT use the 0H setting without the assistance from local agent. Improper use is not incorporated in the warranty. Step 4: Press and hold the toggle for 4 seconds to save the setting value and return to general mode. Copyright © 2014 CyberPower Systems, Inc.
  • Page 13  The voltage differences of one set of batteries shall be within 0.3V. If not, change the unsuitable batteries in order not to cause unbalanced charge. It will shorten the lifespan of batteries. Copyright © 2014 CyberPower Systems, Inc.
  • Page 14: Fault Warning Display And Alarm

    Overcharge in Line Mode Inform service agents. After warning, all above except “Battery missing in Line Mode” will all shut down. For “Battery missing in Line Mode”, the On Battery icon will keep flashing. Copyright © 2014 CyberPower Systems, Inc.
  • Page 15 After the EPS shutdown, the Fault Mode icon will also illuminate on the LCD display together with the error code, indicating there is a problem with the machine. Please contact CyberPower Systems or local agent for further help and support.
  • Page 16: Replacing The Battery

    Do not open or mutilate the batteries. Released electrolyte is harmful to skin and eyes and may be toxic. CAUTION! The external battery cabinet must be provided with 80V / 100A for model CPS1500PIE. CPS1500PIE Series include CPS1500PIE, CPS1500PIE-FR, CPS1500PIE-UK and other versions. CAUTION! A battery can present a risk of electrical shock and high short-circuit current.
  • Page 17: Troubleshooting

    Mechanical problem. local agent via phone or visit our website. Input and output wiring Check the input/output connection. error The battery voltage is too Check the reason for battery high during cold start. over-voltage. Copyright © 2014 CyberPower Systems, Inc.
  • Page 18: Technical Specifications

    On Battery, Low Battery, Overload, Overheat, Overcharge Environmental Temperature 32℉ to 104℉ (0℃ to 40℃) Relative Humidity 0 to 95% Non-Condensing Physical Dimensions (LxWxH) (mm) 261 x 206 x 325 Weight (Kg) 18.6 Kg Safety Certificated CE/SONCAP Copyright © 2014 CyberPower Systems, Inc.
  • Page 19 CPS1500PIE For more information, contact us at: CyberPower Systems, Inc. Website: www.cpsww.com Entire contents copyright © 2014 CyberPower Systems, Inc. All rights reserved. Reproduction in whole or in part without permission is prohibited. Copyright © 2014 CyberPower Systems, Inc.

Table of Contents