Program Example - Mitsubishi FX3U-USB-BD User Manual

Melsec-f fx series programmable controllers
Hide thumbs Also See for FX3U-USB-BD:
Table of Contents

Advertisement

FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
8.2.3

Program example

1. Writing parameters to an inverter while the PLC is in RUN mode
M8002
Initial pulse
M10
Driving of
write
instruction
*1.
When using an E500 Series inverter, use "H2" to specify computer link operation.
FNC180
K11
EXTR
FNC180
K11
EXTR
FNC180
K13
EXTR
FNC180
K13
EXTR
FNC180
K13
EXTR
FNC180
K13
EXTR
M8029
Instruction execute
complete
8 Practical Program Examples (for FX2N and FX2NC PLCs)
SET
M10
The write
instruction
is driven
K0
H0FD
H9696
The inverter is reset
Computer link
K0
H0FB
H0
*1
operation is specified
The maximum
K0
K1
K12000
frequency is set to
"120Hz"
The minimum
K0
K2
K500
frequency is set to
"5Hz"
The acceleration time
K0
K7
K10
is set to "1s"
The deceleration time
K0
K8
K10
is set to "1s"
RST
M10
The write
instruction
is driven
8.2 Practical Example 2
A
B
C
D
E
F
G
H
I
Apx.
E-79