Configuring/address space
4.4 Parameters
Parameters of the TM PTO 4
The following parameter settings are possible:
Table 4- 4
Configurable parameters and their defaults
Parameter
Channel configuration
Signal type
Signal interface
Interpulse period follow-
ing
auto reverse
Enable diagnostic
interrupts
Increments per
revolution
Reference speed
Maximum speed
30
Value range
4 channels
4 channels
•
3 channels
•
2 channels
•
1 channel
•
Pulse (P) and direc-
Pulse (P) and
•
tion (D)
direction (D)
Count up (A),
•
count down (B)
Incremental en-
•
coder (A, B phase-
shifted)
Incremental en-
•
coder (A, B phase-
shifted, quadruple)
24 V, asymmetrical
24 V, asymmet-
•
rical
RS422, symmet-
•
rical / TTL (5 V),
asymmetrical
0 ms
0 ms
•
1 ms
•
4 ms
•
10 ms
•
Disabled
Disabled
•
Enabled
•
1...1000000
200
1,0...20000,0 U/min
3000,0
Dependent on signal
3000,0
interface, signal eval-
uation, increments per
revolution and refer-
ence speed (see
following table)
Default setting
Re-configuration in
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Technology Module TM PTO 4 (6ES7553-1AA00-0AB0)
Effective range with
RUN
configuration
software: HSP or
GSD file for
PROFINET IO
Module
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Manual, 12/2016, A5E38896703-AA