Powerware 9315 UPS Operation Manual page 72

200–300 kva
Hide thumbs Also See for 9315 UPS:
Table of Contents

Advertisement

Product Specifications
Table 9-3. System Output
Rectifier/Charger Capacity
DC Filtering
UPS Output Capacity
Output Voltage Regulation
Output Voltage Adjustment
(Nominal +/–5%)
Output Voltage Harmonic Content
Output Voltage Balance
Output Voltage Phase
Displacement
Output Transients
Frequency Regulation
Synchronous to Bypass
Frequency Slew Rate
Overload Capability
Maximum Output Capability
Table 9-4. Environmental Specifications
Operating Temperature
Operating Altitude
Storage Temperature
Relative Humidity (operating and
storage)
Acoustical Noise
EMI Suppression
Electrostatic Discharge (ESD)
Immunity
9−2
EATON Powerware
125%
Ripple voltage less than 0.5% peak to peak
100% rated current
1% (10% to 100% load)
208 Vac nominal, adjustable from 198 Vac to 218 Vac (60 Hz only)
480 Vac nominal, adjustable from 456 Vac to 504 Vac (60 Hz only)
600 Vac nominal, adjustable from 570 Vac to 630 Vac (60 Hz only)
400 Vac nominal, adjustable from 380 Vac to 420 Vac (50/60 Hz)
3% max THD, 2% max single (linear load)
3% for 100% maximum load imbalance
3° for 100% maximum load imbalance
"5% for 100% load step or removal
"0.01 Hz free running
Bypass within voltage limits of +5%, –8% of output setting; bypass within
±0.5 Hz
1 Hz per second maximum (adjustable)
125% for 10 minutes
150% for 10 seconds
300% peak for 10 cycles without bypass
0 to 40°C without derating. However, operating at or near 40°C will
adversely affect battery life (refer to your battery specifications for more
information). The recommended operating temperature is 25°C.
Maximum 1500m (5000 ft) at 40°C without derating
–20 to +70°C (prolonged storage above 40°C will cause rapid battery
self-discharge)
95% maximum noncondensing
65 dBA at a 1m distance
Meets FCC Regulation 47, Part 15, Subpart J, for class A devices
Meets IEC 801-2 specifications. Withstands up to 25 kV without damage and
with no disturbance or adverse effect to the critical load.
9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
®

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

9315

Table of Contents