Communication

7.7.3 Enable/Disable Default Functions

From this menu you may either enable the building alarms for general functions or special
functions such as On Generator, Go To Bypass, and Go To UPS. You may also customize the
alarm messages from this menu. When 1 is selected from this menu, the following menu is
displayed:
If you select entry 1−3 from this menu, the following menu appears:
Where (Function) indicates the function the building alarm is being programmed for. The
line following the Enabled Building Alarm Number(s) label indicates which building alarms
are currently enabled for the function. (In this example, Building Alarms 1 and 4 are
enabled.) A building alarm can only be programmed for one special function at a time
from these menus. Enabling a building alarm for a special function automatically enables
the alarm. If you disable a special function, the building alarm is also disabled.
If you select entry 4 from this menu, the following menu appears:
The line following the Enabled Building Alarm Number(s) label indicates which building
alarms are currently enabled. (In this example, Building Alarms 1 and 4 are enabled.)
7−14
EATON Powerware
Enable/Disable Default Functions
1. Enable/Disable Go To Bypass
2. Enable/Disable Go To UPS
3. Enable/Disable On Generator
4. Enable/Disable Building Alarm
5. Return to Program Building Alarms Menu
Enter Selection:
Enable/Disable (Function)
Enabled Building Alarm Number(s)
1 4
Enter E# to Enable Building Alarm Number #
Enter D# to Disable Building Alarm Number #
Enter <CR> for No Change
Enter Selection:
Enable/Disable Building Alarm
Enabled Building Alarm Number(s)
1 4
Enter E# to Enable Building Alarm Number #
Enter D# to Disable Building Alarm Number #
Enter <CR> for No Change
Enter Selection: