5 Installation and Wiring
5-3
Wiring
This section describes wiring methods for the CPU Unit.
5-3-1
Wiring Procedure
Make sure that the power supply is OFF before beginning wiring.
1. Prepare the parts required for wiring.
2. Connect the power supply terminals.
3. Ground the ground terminal(
4. Connect the input terminals.
5. Connect the output terminals.
5-3-2
Wiring Power Supply and Ground Lines
Wiring AC Power Supply and Ground
LG: Functional ground terminal
• Wire a separate circuit for the power supply circuit so that there is no voltage drop from the inrush
current or startup current that flows when other equipment is turned ON.
• When several CP1E PLCs are being used, it is recommended to wire the PLCs on separate cir-
cuits to prevent a voltage drop from the inrush current or incorrect operation of the circuit breaker.
5-14
Prepare crimp terminals and cables for
wiring.
Connect power supply to power supply
terminals L1 and L2/N.
Ground to 100 Ω or less.
).
Connect sensors and switches to the
terminals.
Connect loads to the terminals.
100 to 240 VAC, 50/60 Hz
R
S
MCCB
Upper Terminal Block
L1
L2/N COM
01
03
00
02
GR: Protective ground terminal
Ground to 100 Ω or less
Refer to 5-3-2 Wiring Power Supply
and Ground Lines.
Refer to 5-3-2 Wiring Power Supply
and Ground Lines.
Refer to 5-3-3 I/O Wiring.
Refer to 5-3-3 I/O Wiring.
05
07
09
11
01
04
06
08
10
00
02
CP1E CPU Unit Hardware User's Manual(W479)
−