Dynamic Drive Control - Siemens SINAMICS G120C USS/MB Operating Instructions Manual

Sinamics g120c series low voltage converter built-in units with frame sizes aa - f
Hide thumbs Also See for SINAMICS G120C USS/MB:
Table of Contents

Advertisement

Commissioning
5.5 Quick commissioning with a PC
5.5.7

Dynamic Drive Control

Procedure for application class [2]: Dynamic Drive Control
Select the I/O configuration to preassign the inverter interfaces.
Set the applicable motor standard and the inverter supply voltage.
Select your motor.
Enter the motor data according to the rating plate of your motor.
If you have selected a motor based on its article number, the data has already been entered.
Set the most important parameters to suit your application.
Application:
● [0]: Recommended setting for standard applications.
● [1]: Recommended setting for applications with ramp-up and ramp-down times < 10 s. This
setting is not suitable for hoisting gear and cranes.
● [5] Recommended setting for applications with a high break loose torque.
Motor data identification:
● [0]: No motor data identification
● [1]: Recommended setting. Measure the motor data at standstill and with the motor rotating.
The inverter switches off the motor after the motor data identification has been completed.
● [2]: Default setting: Measure the motor data at standstill. The inverter switches off the motor
after the motor data identification has been completed.
Select this setting if the motor cannot freely rotate, e.g. for a mechanically limited traversing
range.
● [3]: Measure the motor data while it is rotating. The inverter switches off the motor after the
motor data identification has been completed.
● [11]: The same setting as [1]. The motor accelerates to the currently set setpoint after the
motor data identification.
● [12]: The same setting as [2]. The motor accelerates to the currently set setpoint after the
motor data identification.
You have completed quick commissioning.
144
Factory setting of the interfaces (Page 88)
Default setting of the interfaces (Page 91)
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF