8-3. Recommended Wire Length and Diameter

Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your
local electrical codes. Carefully observe these regulations when carrying out the installation.
Table 2 lists recommended wire lengths and diameters for power supply systems.
NOTE
Refer to the wiring system diagram (Fig. 8) for the meaning of "A" and "B" in Table 2.
Table 2
Cross-Sectional
Area (mm
Model
CMV2441G
WARNING
WARNING
CAUTION
Control Line Length (A)
2
)
1.0
20 m
NOTE
SAP-KMV91: Unit A to D
SAP-KMV91: Unit A to C
SAP-KMV181: Unit D
Unit D
Be sure to comply with local codes on running the wire from the
indoor unit to the outdoor unit (size of wire and wiring method, etc.).
Each wire must be firmly connected.
No wire should be allowed to touch refrigerant tubing, the com-
pressor, or any moving part.
Be sure to connect power wires correctly matching up numbers on
terminals of the outdoor unit and respective indoor units A – D.
To avoid the risk of electric shock, each air conditioner unit must
be grounded.
Be sure to connect the power supply line to the outdoor unit as
shown in the wiring diagram. The indoor unit draws its power from
the outdoor unit.
Power Line Length (B)
2.5
4.0
16 m
27 m
Indoor unit
Unit A
1
2
4
Unit B
1
2
4
Unit C
1
2
4
Unit D
1
1
2
2
4
4
5
(A)
29
Fuse or Circuit Capacity
20 A
WIRING SYSTEM DIAGRAM
Outdoor unit
Terminal plate (16P)
1
2
4
1
2
4
1
2
4
1
2
4
Terminal plate (3P)
1
2
Grounding line
Power supply
Single-phase, 220 – 230 VAC
Fig. 8
(B)
Power
Unit A
Cont
Power
Unit B
Cont
Power
Unit C
Cont
Power
Unit D
Cont