Sanyo SAP–K91GJA (?2) Technical & Service Manual

Sanyo SAP–K91GJA (?2) Technical & Service Manual

Multi-split system air conditioner

Advertisement

TECHNICAL & SERVICE MANUAL
SAP – K91GJA (
SAP – K91GJA (
SAP – K91GJA (
MULTI-SPLIT SYSTEM AIR CONDITIONER
Indoor Model No
SAP – K91GJA– S
SAP – K91GJA– S
SAP – K91GJA– S
SAP–K91GJA ( 2)
SAP–K91GJA ( 2)
SAP–K91GJA ( 2)
2 ) + SAP – CM1621GA
2 ) + SAP – CM1821GA
2 ) + SAP – CM1821JA
Product Code No.
1 852 070 37
1 852 070 37
1 852 070 37
Indoor Unit
FILE NO.
Outdoor Model No.
Product Code No.
SAP – CM1621GA– S
1 852 071 48
SAP – CM1821GA– S
1 852 071 49
SAP – CM1821JA– S
1 852 071 50
Outdoor Unit
SAP–CM1621GA
SAP–CM1821GA
SAP–CM1821JA
REFERENCE NO.
Destination: General (50Hz)
General (60Hz)
SM
700468

Advertisement

Table of Contents
loading

Summary of Contents for Sanyo SAP–K91GJA (?2)

  • Page 1 TECHNICAL & SERVICE MANUAL SAP – K91GJA ( 2 ) + SAP – CM1621GA FILE NO. SAP – K91GJA ( 2 ) + SAP – CM1821GA SAP – K91GJA ( 2 ) + SAP – CM1821JA Destination: General (50Hz) General (60Hz) MULTI-SPLIT SYSTEM AIR CONDITIONER Indoor Model No Product Code No.
  • Page 2: Special Precautions

    IMPORTANT! Please Read Before Starting When Installing… This air conditioning system meets strict safety and operat- ing standards. As the installer or service person, it is an …In a Ceiling or Wall important part of your job to install or service the system Make sure the ceiling/wall is strong enough to hold the so it operates safely and efficiently.
  • Page 3: Table Of Contents

    Table of Contents Page Unit Combination............................ iii 1. OPERATING RANGE ..........................1 2. SPECIFICATIONS 2-1. Unit Specifications .......................... 2 2-2. Major Component Specifications....................5 2-3. Other Component Specifications....................9 3. DIMENSIONAL DATA..........................10 4. COOLING CAPACITY ..........................12 5. AIR THROW DISTANCE CHART ......................18 6.
  • Page 4: Unit Combination

    Unit Combination Combine indoor and outdoor units only as listed below. Symbol of Outdoor Unit Indoor Unit Refer to Indoor Unit K91GJA SAP–CM1621GA Fig.1 K91GJA K91GJA SAP–CM1821G Fig.1 K91GJA K91GJA SAP–CM1821JA Fig.1 K91GJA Indoor Unit Outdoor Unit Fig.1 Fi 1...
  • Page 5: Operating Range

    1. OPERATING RANGE Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 32°C D.B. / 23°C W.B. 43°C D.B. Cooling Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
  • Page 6: Specifications

    2. SPECIFICATIONS 2-1. Unit Specifications Indoor Unit SAP – K91GJA Outdoor Unit SAP – CM1621GA No. of indoor units. 1-unit 2-units Power Source 220 / 230 / 240 V Single phase 50 Hz Cooling Capacity 2.30 4.60 BTU/h 7,800 15,700 m 3 /h Air circulation (High) 430 2...
  • Page 7 Indoor Unit SAP – K91GJA Outdoor Unit SAP – CM1821GA No. of indoor units. 1-unit 2-units Power Source 220 / 230 / 240 V Single phase 50 Hz Cooling Capacity 2.60 5.20 BTU/h 8,900 17,700 m 3 /h Air circulation (High) 430 2 Moisture removal (High) Liters/h...
  • Page 8 Indoor Unit SAP – K91GJA Outdoor Unit SAP – CM1821JA No. of indoor units. 1-unit 2-units Power Source 220V Single phase 60 Hz Cooling Capacity 2.60 5.20 BTU/h 8,900 17,700 m 3 /h Air circulation (High) 430 2 Moisture removal (High) Liters/h 0.85 0.85 2...
  • Page 9: Major Component Specifications

    2-2. Major Component Specifications 2-2-1. Indoor Unit Indoor Unit SAP – K91GJA Part No. POW–K91GJA Controls Microprocessor Control circuit fuse 250 V – 3.15 A Remote Control Unit RCS–2S2E Type Cross–flow Number ... Dia. and length 1 ... ø95 / L578 Fan motor model ...
  • Page 10: Outdoor Unit

    2-2-2. Outdoor Unit Outdoor Unit SAP – CM1621GA Type Rotary (Hermetic) Compressor model ... Number C–1R71H5U ... 2 / 80688745 – S ... 2 Nominal output Compressor oil ... Amount 4GS D –T or SAY-56T ... 320 2 Ω Coil resistance (Ambient temp. 25°C) C –...
  • Page 11 Outdoor Unit SAP – CM1821GA Type Rotary (Hermetic) Compressor model ... Number C – 1R80H5K ... 2 / 80603345 – S ... 2 Nominal output Compressor oil ... Amount 4GS D –T or SAY-56T ... 320 2 Ω Coil resistance (Ambient temp. 25°C) C –...
  • Page 12 Outdoor Unit SAP – CM1821JA Type Rotary (Hermetic) Compressor model ... Number C – 1R71H6U ... 2 / 80688746– S ... 2 Nominal output Compressor oil ... Amount 4GS D –T or SAY-56T ... 320 2 Ω Coil resistance (Ambient temp. 25°C) C –...
  • Page 13: Other Component Specifications

    2-3. Other Component Specifications Indoor Unit SAP – K91GJA Transformer (TR) ATR-J105 Rating Primary AC 230V, 50 / 60 Hz Secondary 19V, 0.526A Capacity 10VA Ω (at 21°C) Coil resistance Primary (WHT – WHT): 205 ± 10% Secondary (BRN – BRN): 2.0 ±...
  • Page 14: Dimensional Data

    3. DIMENSIONAL DATA Indoor Unit SAP – K91GJA Remote control unit 58.5 Center of tubing Drain hose ø18 hole (2 places) Narrow tube ø6.35 (1/4") Wide tube ø9.52 (3/8") Unit : mm...
  • Page 15 Outdoor Unit SAP – CM1621GA SAP – CM1821GA SAP – CM1821JA AIR INTAKE AIR DISCHARGE Wide tube service valve ø9.52 (3/8") Narrow tube service valve ø6.35 (1/4") Unit : mm...
  • Page 16: Cooling Capacity

    4. COOLING CAPACITY 1 - indoor unit in operation A(or B) Indoor Unit SAP – K91GJA ( 1) NOTE Outdoor Unit SAP – CM1621GA A : SAP–K91GJA 230 V Single phase 50 Hz B : SAP–K91GJA RATING CAPACITY 2.30 kW EVAPORATOR CONDENSER ENT.
  • Page 17 2 - indoor units in operation A + B Indoor Unit SAP – K91GJA ( 2) NOTE Outdoor Unit SAP – CM1621GA A : SAP–K91GJA B : SAP–K91GJA 230 V Single phase 50 Hz RATING CAPACITY 4.60 kW EVAPORATOR CONDENSER ENT.
  • Page 18 1 - indoor unit in operation A(or B) Indoor Unit SAP – K91GJA ( 1) NOTE Outdoor Unit SAP – CM1821GA A : SAP–K91GJA B : SAP–K91GJA 230 V Single phase 50 Hz RATING CAPACITY 2.60 kW EVAPORATOR CONDENSER ENT. TEMP. °C OUTDOOR AMBIENT TEMP.
  • Page 19 2 - indoor units in operation A + B Indoor Unit SAP – K91GJA ( 2) NOTE Outdoor Unit SAP – CM1821GA A : SAP–K91GJA B : SAP–K91GJA 230 V Single phase 50 Hz RATING CAPACITY 5.20 kW EVAPORATOR CONDENSER ENT.
  • Page 20 1 - indoor unit in operation A(or B) Indoor Unit SAP – K91GJA ( 1) NOTE Outdoor Unit SAP – CM1821JA A : SAP–K91GJA B : SAP–K91GJA 220 V Single phase 60 Hz RATING CAPACITY 2.60 kW EVAPORATOR CONDENSER ENT. TEMP. °C OUTDOOR AMBIENT TEMP.
  • Page 21 2 - indoor units in operation A + B Indoor Unit SAP – K91GJA ( 2) NOTE Outdoor Unit SAP – CM1821JA A : SAP–K91GJA B : SAP–K91GJA 220 V Single phase 60 Hz RATING CAPACITY 5.20 kW EVAPORATOR CONDENSER ENT.
  • Page 22: Air Throw Distance Chart

    5. AIR THROW DISTANCE CHART Indoor Unit SAP – K91GJA Room air temp. : 27°C Fan speed High Horizontal distance (m) : Flap angle 0° , : Axis air velocity 0° : Flap angle 30°, : Axis air velocity 30°...
  • Page 23: Refrigerant Flow Diagram

    6. REFRIGERANT FLOW DIAGRAM Indoor Unit SAP – K91GJA ( 2) SAP – K91GJA ( 2) SAP – K91GJA ( 2) Outdoor Unit SAP – CM1621GA SAP – CM1821GA SAP – CM1821JA Outdoor Unit Indoor Unit A Accumulator Wide tube O.D.
  • Page 24: Electrical Data

    7. ELECTRICAL DATA 7-1. Electrical Characteristics Indoor Unit SAP – K91GJA ( 1) Outdoor Unit SAP – CM1621GA Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 230V Single phase 50Hz Rating Conditions Running Amps. 0.18 0.49 2.83 Power Input...
  • Page 25 Indoor Unit SAP – K91GJA ( 1) Outdoor Unit SAP – CM1821GA Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 230V Single phase 50Hz Rating Conditions Running Amps. 0.18 0.49 4.13 Power Input 0.037 0.112 0.851 1.00 Full Load Conditions Running Amps.
  • Page 26 Indoor Unit SAP – K91GJA ( 1) Outdoor Unit SAP – CM1821JA Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220V Single phase 60Hz Rating Conditions Running Amps. 0.15 0.52 3.93 Power Input 0.031 0.114 0.815 0.96 Full Load Conditions Running Amps.
  • Page 27: Electric Wiring Diagrams

    7-2. Electric Wiring Diagram To avoid electrical shock hazard, be sure to disconnect power before checking, servicing WARNING and/or cleaning any electrical parts. Indoor Unit SAP – K91GJA...
  • Page 28 To avoid electrical shock hazard, be sure to disconnect power before checking, servicing WARNING and/or cleaning any electrical parts. Outdoor Unit SAP – CM1621GA SAP – CM1821GA SAP – CM1821JA...
  • Page 29: Installation Instructions

    8. INSTALLATION INSTRUCTIONS           8-1. Installation Site Selection Tubing length (L) INDOOR Maximum Allowable Tubing Length(L)and Elevation UNIT Difference(H). Less than elevation The Multi-Split System outdoor unit should be installed as difference (H) between OUTDOOR close to the indoor units as possible.
  • Page 30 Outdoor Unit AVOID: heat sources, exhaust fans, etc. (Fig. 3) damp, humid or uneven locations. Exhaust fan Hot air Heat source choose a place as cool as possible. Outdoor unit choose a place that is well ventilated. allow enough room around the unit for air intake/exhaust and possible maintenance.
  • Page 31: Remote Control Unit Installation Position

    7-2. Remote Control Unit Installation Position The remote control unit can be operated from either a non-fixed position or a wall-mounted position. To ensure that the air conditioner operates correctly, do not install the remote control unit in the following places: In direct sunlight Behind a curtain or other place where it is covered More than 8 m away from the air conditioner...
  • Page 32: Recommended Wire Length And Diameter

    8-3. Recommended Wire Length and Diameter Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Carefully observe these regula- tions when carrying out the installation. Table 2 lists recommended wire lengths and size for power supply systems.
  • Page 33: Function

    9. FUNCTION 9-1. Room Temperature Control Room temperature control is obtained by cycling the compressor ON and OFF under control of the room tem- perature sensor in the remote control unit. The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the controller in the indoor unit.
  • Page 34: Dry Operation

    9-2. Dry Operation (Dehumidification) Dry operation uses the ability of the cooling cycle to remove moisture from the air, but by running at low level to dehumidify without greatly reducing the room temperature. The air conditioner repeats the cycle of turning ON and OFF automatically as shown in the chart below according to the room temperature.
  • Page 35: Troubleshooting

    10. TROUBLESHOOTING 10-1. Check before and after troubleshooting WARNING Hazardous voltage can cause ELECTRIC SHOCK or DEATH. Disconnect power or turn off circuit breaker before you start checking or servicing. 10-1-1. Check power supply wiring. Check that power supply wires are correctly connect- ed to terminals No.1 and No.2 on the terminal plate in Power supply the outdoor unit.
  • Page 36: Air Conditioner Does Not Operate

    10-2. Air conditioner does not operate. 10-2-1. Circuit breaker trips (or fuse blows). A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.) There is a possibility of ground fault. Check insulation resistance. If resistance value is 2MΩ...
  • Page 37 B.Circuit breaker trips in several minutes after turning the air conditioner on. There is a possibility of short circuit. • Check capacity of circuit breaker. Replace with suitable one (larger capacity). Capacity of circuit breaker is suitable. Measure resistance of outdoor fan •...
  • Page 38 10-2-2. Neither indoor nor outdoor unit runs. A. Power is not supplied. Circuit breaker Reset breaker. is tripped. • Check power supply. Power is being supplied to the Wait for recovery outdoor unit. Power failure or contact power company. B. Check remote control unit. Does not run.
  • Page 39 E. Check fuse on the indoor PCB Ass'y. • Measure resistance of indoor fan If fuse has been blown, • Check fuse on indoor PCB Ass'y motor winding. for continuity. (FMI ) • Check operation lamp to see • Measure resistance of flap motor if light is ON.
  • Page 40 10-2-3. Only outdoor unit does not run. A. Check setting temperature. Is room temperature too low ? Try to lower setting temperature by temperature setting button cooler. Outdoor unit still does not run. • Try to run using another remote control unit.
  • Page 41: Some Part Of Air Conditioner Does Not Operate

    10-3. Some part of air conditioner does not operate. 10-3-1. Only indoor fan does not run. • Check fan casing Remove foreign foreign matter on matter or repair. Fan cannot inside. be turned. • Check fan rotation. Turn fan gently once or twice by hand.
  • Page 42 10-3-3. Only compressor does not run. • Check compressor moter overload relay is working. (OLR 1 to 4) capacitor. (C2, C3) • Measure resistance of Temperature of compressor is abnormally high. compressor motor winding. Refrigerant gas shortage. Charge refrigerant gas (R22). •...
  • Page 43: Air Conditioner Operates, But Abnormalities Are Observed

    10-4. Air conditioner operates, but abnormalities are observed. 10-4-1. Poor cooling. • Check position of remote control unit. Change position of remote Cool air from air conditioner reaches • control unit. position directly. • Wide and narrow tubes between Insulate both wide and narrow indoor unit and outdoor unit are tubes separately and then insulated.
  • Page 44: If A Sensor Is Defective

    10-5. If a sensor is defective. 10-5-1. Indoor coil temp. thermistor (TH1) is defective. • Operation lamp on front side of • Thermistor (TH1 ) is defective. indoor unit is flashing on and off. (*) (That is, sensor is SHORT.) •...
  • Page 45: Arrangement Of Electrical Component

    11. ARRANGEMENT OF ELECTRICAL COMPONENT Outdoor Unit SAP – CM1621GA SAP – CM1821GA SAP – CM1821JA Electric Parts Overload relay 3 (B) Overload relay 1(A) Power relay B (PRB) Fan motor capacitor C1 Power relay A (PRA) Compressor motor capacitor (C3) Compressor motor capacitor (C2 ) Terminal plate 4 5 6 7 8 9 101112...
  • Page 46: Checking Electrical Components

    12. CHECKING ELECTRICAL COMPONENTS 12-1. Measurement of Insulation Ground wire Resistance Clip The insulation is in good condition if the resistance exceeds 2MΩ. 12-1-1. Power Supply Wires Probe Clamp the ground wire of the power supply wires with Insulation Fig. 1 tester the lead clip of the insulation resistance tester and mea- sure the resistance by placing a probe on either of the...
  • Page 47: Checking Continuity Of Fuse On Pcb Ass'y

    12-2. Checking Continuity of Fuse on PCB Ass'y Fuse Remove the PCB Ass'y from the electrical component box. Then pull out the fuse from the PCB Ass'y. Check for continuity using a multimeter as shown in Fig. 6. PCB Ass’y 12-3.
  • Page 48: Maintenance

    13. MAINTENANCE 13-1. Changing Address of Remote Control Unit in Indoor Unit If you are installing more than 1 indoor unit (up to 2) in the same room, it is necessary for you to assign each unit its own address, so each can be operated by its own separate remote control unit. You assign the addresses by matching the remocon address on the PCB of each indoor unit with the switch positions of its remote control unit.
  • Page 50 SANYO Electric Co.,Ltd. Osaka, Japan 700468 11/00/200 Printed in Japan...