Viewing the TD 200 Parameter Block and Messages

The TD 200 Configuration Wizard creates a data block containing the TD 200 parameter
block and messages. You can open the data block editor to view the TD 200 parameter
block and messages that were formatted by the wizard. Figure 2-17 shows the data block for
the example in this chapter.
DB
Data Block Editor
// BEGIN TD200_BLOCK 0
// (Comments within this block should not be edited or removed)
VB0
'TD'
// TD 200 Identification
VB2
16#10
// Set Language to English, set Update to As fast as possible
VB3
16#71
// Set the display to 40 character mode; Up key V3.2; Down key V3.3
VB4
3
// Set the number of messages
VB5
0
// Set the Function Keys notification bits to M0.0 – M0
VW6
40
// Set the starting address for messages to VW40
VW8
12
// Set the starting address for message enable bits to VW12
VW10
1111
// Global Password
// MESSAGE 1
// Message Enable Bit V12.7
VB40
'PRESS F1 TO DISPLAY THE NEXT MESSAGE ...'
// MESSAGE 2
// Message Enable Bit V12.6
VB80
'PREV. SETPOINT:
VB96
16#00
// No Edit; No Acknowledgement; No Password
VB97
16#11
// Signed Word; 1 Digits to the right of the decimal;
VW98
16#00
// Embedded Data Value: Move data for display here.
VB100 'NEW SETPOINT: '
VB114 16#18
// Edit Notification V114.2; No Acknowledgement; Edit Requires Passw
VB115 16#51
// Real Double Word; 1 Digits to the right of the decimal;
VD116 16#0000
// Embedded Data Value: Move data for display here.
// MESSAGE 3
// Message Enable Bit V12.5
VB120 'ACKNOWLEDGE MESSAGE BY PRESSING ENTER:'
VB158 16#01
// No Edit; Acknowledgement Notification V158.1; No Password
VB159 16#00
// No Data; 0 Digits to the right of the decimal;
// END TD200_BLOCK 0
Figure 2-17 Data Block Editor Showing a Sample TD 200 Parameter Block
SIMATIC TD 200 Operator Interface
C79000-G7076-C205-04
'
Configuring the TD 200
2-17