13.1.10

3RW30 auxiliary conductor cross-sections

13.1.11

Electromagnetic compatibility according to EN 60947-4-2

Electromagnetic compatibility according to EN 60947-4-2
EMC interference immunity
Electrostatic discharge (ESD)
Electromagnetic RF fields
Conducted RF interference
RF voltages and RF currents on cables
• Burst
• Surge
EMC interference emission
EMC interference field strength
Radio interference voltage
Radio interference suppression filters
Degree of noise suppression A (industrial applications)
Degree of noise suppression B (applications for residential areas)
Control voltage
• 230 V AC/DC
• 24 V AC/DC
1) Degree of noise suppression B cannot be obtained through the use of
filters as the strength of the electromagnetic field is not attenuated by the
filter.
SIRIUS 3RW30 / 3RW40
Manual, 01/2010, 535 1995-02 DS01
Standard
Parameters
±4 kV contact discharge, ±8 kV air discharge
EN 61000-4-2
EN 61000-4-3
Frequency range: 80 to 2000 MHz with 80% at 1 kHz
Degree of severity 3: 10 V/m
EN 61000-4-6
Frequency range: 150 kHz...80 MHz with 80% at 1 kHz
Interference 10 V
±2 kV / 5 kHz
EN 61000-4-4
±1 kV line to line
EN 61000-4-5
±2 kV line to ground
EN 55011
Limit value of Class A at 30...1000 MHz,
Limit value of Class B for 3RW302.; 24 V AC/DC
EN 55011
Limit value of Class A at 0.15...30 MHz,
Limit value of Class B for 3RW302.; 24 V AC/DC
Not required
1)
Not available
Not required for 3RW301. and 3RW302;
Required for 3RW303. and 3RW304. (see table)