Connectable Conductor Cross-Sections For Screw Terminals - Siemens SINAMICS S120M Manual

Distributed drive technology
Hide thumbs Also See for SINAMICS S120M:
Table of Contents

Advertisement

If DRIVE-CLiQ Extension (DQE) and/or Hybrid Cabinet Bushing (HCB) are used, the
permissible cable length can be calculated as follows:
Σ Hybrid + n
Σ Hybrid: Total length of all Hybrid Cable sections
Σ MOTION-CONNECT 500 = standard length - segment DQE to following S120M - n
Σ MOTION-CONNECT 800PLUS = standard length - segment DQE to following S120M -
n
• 5 m
c
n
: Number of DQE (theoretically unrestricted) + number of HCB (0-3 max.)
c
Example of MOTION-CONNECT 500 (segment length 10 m, 1 DQE, 1 HCB):
100 m - 10 m - 5 m • 2 = <100 m
7.3.8

Connectable conductor cross-sections for screw terminals

The type of screw terminal can be taken from the interface description of the particular
component.
Table 7- 8
Screw terminals
Screw terminal type
1 (X21 AM600)
5 (X24)
(24 V terminal adapter)
SINAMICS S120M Distributed Drive Technology
Manual, (GH12), 12/2014, 6SL3097-4AW00-0BP3
• 5 m ≤ 100 m
c
Connectable conductor
cross-sections
Stripping length
Tool
Tightening torque
Connectable conductor
cross-sections
Stripping length
Tool
Tightening torque
Rigid, flexible
With wire end ferrule, without plastic
sleeve
With wire end ferrule, with plastic sleeve
7 mm
Screwdriver 0.4 x 2.0 mm
0.22 to 0.25 Nm
Flexible
With wire end ferrule, without plastic
sleeve
With wire end ferrule, with plastic sleeve
12 mm
Screwdriver 1.0 x 4.0 mm
1.2 to 1.5 Nm
Cabinet design and EMC S120M
7.3 Connection system
0.08 mm
to 1.5 mm
2
0.25 mm
to 1.5 mm
2
0.25 mm
to 0.5 mm
2
0.5 mm
to 6 mm
2
0.5 mm
to 6 mm
2
0.5 mm
to 6 mm
2
• 5 m
c
2
2
2
2
2
2
135