Codes for output types
The following table contains the codes for the output types of the analog output module. You
enter this coding in byte x (see previous figure).
Table A- 1
Output type
Deactivated
Current
Codes for output ranges
The following table contains the codes for the output ranges of the analog output module.
You enter these codes in byte x+1 of data record 128 (see previous figure).
Table A- 2
Output range
Current
±20 mA
0 mA to 20 mA
4 mA to 20 mA
Value range for substitute value
The following table contains the value ranges for the substitute values. You must enter the
corresponding codes in bytes x+4 and x+5 (see previous figure).
Output range
Current
±20 mA
0 mA to 20 mA
4 to 20 mA
28
Codes for output types
Codes for output ranges
Code
0000 0000
0000 0011
Code
0000 0000
0000 0001
0000 0010
Permissible value range
-29031 to 29030
0 to 29030
-692 to 29376
Analog output module AQ 2xI ST (6ES7135-6GB00-0BA1)