Burner control unit
DIP switch setting or parameter set
The DIP switch (at the back of the display and programming unit) is factory-set to the
rated output of the burner. A change to this factory setting is only required for oper-
ation with reduced output.
Note
If another parameter set is selected, this must be acknowledged (see page 38).
Setting
Rated burner output
Parameter set 0
≙ 87 kW
ON
1 2 3 4 5 6 7 8
Parameter set 1
≙ 115 kW
ON
ON
1 2 3 4 5 6 7 8
Parameter set 2
≙ 142 kW
ON
ON
1 2 3 4 5 6 7 8
Parameter set 3
≙ 186 kW
ON
ON
1 2 3 4 5 6 7 8
(cont.)
Setting
Reduced burner output
Parameter set 6
not possible
Parameter set 7
not possible
Parameter set 8
≙ 100 kW
ON
ON
1 2 3 4 5 6 7 8
Parameter set 9
≙ 130 kW
ON
ON
1 2 3 4 5 6 7 8
37