Further details regarding the individual steps
C
D
Checking the condensate drain and the neutralising system (if
installed)
Fill water into the combustion chamber.
Note
The water must flow from the conden-
sate drain without back pressure.
If necessary, clean the condensate drain
again.
B
A
Commissioning, inspection, maintenance
1. Pull drain or cleaning hose C off.
2. Clean the inside of the condensate
drain system (hose, pipe).
3. Clean the neutralising system (if
installed) in accordance with the
manufacturer's instructions.
Neutralising system operating
instructions
Note
You can obtain neutralising agent
from Viessmann quoting part no.
9521 702.
4. Release and flush lower part A of
siphon B.
5. Fill lower part A of siphon B with
water and reassemble.
6. Refit hose D of the neutralising sys-
tem to the siphon.
(cont.)
23