Viessmann VITOCROSSAL 200 Instructions Manual page 17

Gas condensing boiler
Table of Contents

Advertisement

Further details regarding the individual steps
CO
test at the lower output (115 kW
2
to 311 kW)
Commissioning, inspection, maintenance
(cont.)
3. If the CO
content must be adjusted:
2
■ Remove cap B.
■ Turn adjusting screw A in small
increments (3 mm Allen key) until
the CO
content reaches the speci-
2
fied range:
– Turning clockwise
→ CO
content falls
2
– Turning anti-clockwise
→ CO
content rises
2
4. Record the actual value in the report
(on page 61).
1. Press "-" D until the service display
has decremented to "00" (lower out-
put).
2. Check the CO
2
pipe. For permissible CO
see the table on page 16.
content at the flue
content,
2
17