Checking the ionisation current

01. Switch OFF the main isolator.
02. Pull ionisation current cable plug
C.
03. Switch ON the main isolator.
There must be a fault shutdown
after the burner has tried to start.
The fault code "F 25" flashes in dis-
play B.
04. Switch OFF the main isolator.
Note
Test cable no.1 is required when
checking with the Testomatik-Gas.
You can also carry out this test with
a multimeter.
05. Push ionisation current cable plug
C into adaptor D.
06. Push test cable socket A onto the
ionisation electrode.
A
D
C
Commissioning, inspection, maintenance
07. Switch the main isolator ON and
press reset.
08. Check the ionisation current.
Note
Approx. 2 to 3 s after the gas valve
has been opened and during oper-
ation, the ionisation current should
be at least 3 µA.
09. Record the actual value in the report
(on page 61).
10. Switch the main isolator OFF,
remove the test equipment and
reconnect the ionisation cable plug-
in connectors.
11. Switch ON the main isolator.
(cont.)