Check code
Outdoor 7-segment display
Main
remote
Check
controller
code
L30
L30
L31
P01
P03
P03
P04
P04
AMP Air Conditioning
Location
of
detection
Sub-code
Detected indoor
Indoor
External
address
unit
interlock of
indoor unit
I/F
Extended IC
error
Indoor
Indoor fan motor
unit
error
I/F
Discharge
temperature
TD1 error
01: Compressor
IPDU
Activation of
1 side
high-pressure
02: Compressor
SW
2 side
03: Compressor
3 side
Description
System status
Stop of
corresponding
unit
Continued
There is part failure in P.C.
operation
board (I/F).
Stop of
corresponding
unit
All stop
Discharge temperature (TD1)
exceeds 115 "C.
All stop
High-pressure SW is
activated.
77
Error detection
Check items (locations)
condition(s)
Signal is present at
When external device is
external error input
connected to CN80
terminal (CN80) for 1
connector:
minute.
1) Check for defect in
external device.
2) Check for defect in indoor
P.C. board.
When external device is not
connected to CN80
connector:
1) Check for defect in indoor
P.C. board.
Check outdoor P.C. board
(I/F).
Check the lock of fan motor
(AC fan).
Check wiring.
Check outdoor service
valves (gas side, liquid
side) to confirm full
opening.
Check outdoor PMVs
(PMV1, 2, 4) for clogging.
Check resistance
characteristics of TD1
sensor.
Check for insufficiency in
refrigerant quantity.
Check for defect in 4-way
valve.
Check for leakage of SV4
circuit.
Check SV4 circuit (wiring
or installation error in
SV41, SV42 or SV43).
Check connection of high-
pressure SW connector.
Check for defect in Pd
pressure sensor.
Check outdoor service
valves (gas side, liquid
side) to confirm full
opening.
Check for defect in outdoor
fan.
Check for defect in outdoor
fan motor.
Check outdoor PMVs
(PMV1, 2) for clogging.
Check indoor / outdoor
heat exchangers for
clogging.
Check for short-circuiting
of outdoor suction /
discharge air flows.
Check SV2 circuit for
clogging.
Check for defect in outdoor
P.C. board (I/F).
Check for error in indoor
fan system (possible cause
of air flow reduction).
Check opening status of
indoor PMV.
Check indoor-outdoor
communication line for
wiring error.
Check for faulty operation
of check valve in discharge
pipe convergent section.
Check gas balancing SV4
valve circuit.
Check SV5 valve circuit.
Check for refrigerant
overcharging.