Target outdoor unit (SMMS, SHRM, Mini-SMMS – Series 1 – 2)
CODE No.
Indoor unit
00
data
01
02
03
04
05
08
0A
System unit
data
0B
0C
0D
CODE No.
U1 U2 U3 U4
Individual
10 20 30 40
data 1 of
outdoor
11 21 31 41
unit *3
12 22 32 42
13 23 33 43
14
24
34
15
25
35
16
26
36
17
27
37
18
28
38
19
29
39
1A
2A
3A
1B
2B
3B
1C
2C
3C
1D
2D
3D
1E
2E
3E
1F
2F
3F
*1 In the case of group connection, only the header indoor unit data can be displayed.
*2 01 ... Only compressor 1 is on
10 ... Only compressor 2 is on
11 ... Both compressor 1 and 2 are on
*3 The upper digit of CODE No. indicates the outdoor unit No.
U1 outdoor unit (Header unit)
U2 outdoor unit (follower unit 1)
U3 outdoor unit (follower unit 2)
U4 outdoor unit (follower unit 3)
AMP Air Conditioning
Data
Room temperature (in control) *1
Room temperature (Remote controller)
Air Temperature (TA)
Coil Temperature (TCJ)
Coil Temperature (TC2)
Coil Temperature (TC1)
PMV
Number of connected indoor units
Total horse power of connected indoor units
Number of connected outdoor units
Total horse power of outdoor units
Data
Discharge temperature of compressor 1
(Td1)
Discharge temperature of compressor 2
(Td2)
Detection pressure of high-pressure sensor
(Pd)
Detection pressure of low-pressure sensor
(Ps)
44
Suction Temperature (TS)
45
Coil Temperature 1 (TE)
46
Liquid Temperature (TL)
47
Outdoor Temperature (TO)
48
Low-pressure saturation temperature (TU)
49
Current of compressor 1 (I1)
4A
Current of compressor 2 (I2)
4B
PMV1 + 2
4C
PMV3
4D
Compressor 1, 2 ON/OFF
4E
Outdoor fan mode
4F
Horse power of outdoor unit
Format
Unit
×1
˚C
×1
˚C
×1
˚C
×1
˚C
×1
˚C
×1
˚C
×1
pls
×1
×1
HP
×1
×1
HP
Format
Unit
×1
˚C
×1
˚C
×1
MPa
×1
MPa
×1
˚C
×1
˚C
×1
˚C
×1
˚C
×1
˚C
×1
A
×1
A
×1
pls
×1
pls
*2
×1
×1
HP
– 51 –
www.ampair.co.uk | sales@ampair.co.uk
Remote controller display example
[0024]=24 ˚C
[0050]=500 pls
[0048]=48
[0415]=41.5 HP
[0004]=4
[0420]=42 HP
Remote controller display example
[0024]=24 ˚C
[0123]=1.23 MPa
[0024]=24 ˚C
[0135]=13.5 A
[0050]=500 pls
[0050]=500 pls
[0031]=Mode 31
[0016]=16HP