Backing Up Configuration And Log Data; Log Data - Emerson FloBoss 103 Instruction Manual

Hide thumbs Also See for FloBoss 103:
Table of Contents

Advertisement

FloBoss 103/104 Instruction Manual
Warning

3.7 Backing Up Configuration and Log Data

Caution
3-10
It is important to use good wiring practices when sizing, routing, and
connecting power wiring. Ensure that all wiring conforms to state, local,
and NEC codes. The CHG+ / CHG- terminal can accommodate up to 16
AWG wire.
Use only solar panels approved for use with the FB100 in Class 1,
Division 2 locations.
These connections provide the input voltage and power for the battery
charging circuitry. The maximum voltage that can be applied to the
CHG+ / CHG- terminals is 28 volts dc.
This procedure preserves the current flow computer configuration and
log data held in RAM. Perform this backup procedure before you
remove power from the FB100 for repairs, troubleshooting, removing or
adding components, or upgrades.
When installing equipment in a hazardous area, ensure that all
components are approved for use in such areas. Check the product
labels. Change components only in an area known to be non-hazardous.
Performing these procedures in a hazardous area could result in
personal injury or property damage.
To avoid circuit damage when working inside the unit, use appropriate
electrostatic discharge precautions such as wearing a grounded wrist
strap.
1.
Launch ROCLINK 800 software and connect to the FB100.
2.
Ensure that the configuration is saved in flash memory by
performing a Save to Flash Memory (ROC > Flags). This saves all
configuration settings, including the current states of the ROC Flags
and calibration values.
Select ROC > Collect Data and select the All checkbox. Click OK.
3.
This action saves event logs, alarm logs, report data, and history.
You can specify your own file name and path if desired.
Select File > Save. The Save As dialog box appears.
4.
Type the desired File name for the backup file, or use the default.
5.
6.
Click Save. The file is saved in the default directory C:/Program
Files/ROCLINK 800/Data, unless you changed the directory.
Power Connections
Revised August-2017