In these circumstances, remove the battery charger module (part
W38231X0032) and use the FB103 or FB104 without internal power
batteries. Refer to Section 3.5.3, Replacing the Batteries, for instructions
on removing the battery charger module or contact Remote Automation
Solutions LifeCycle Services for assistance in removing the battery
charger module.

Determining Battery Requirements

To determine the system capacity requirements, multiply the system
current load (I
) on the batteries by the amount of reserve time
SF
required. Compute "I
Requirements. The equation is as follows:
System Requirement = I

Replacing the Batteries

The battery pack contains three D-size lead-acid batteries providing 2.5
Amp-hours of current at 6.2 volts nominal.
When installing equipment in a hazardous area, ensure that all
components are approved for use in such areas. Check the product
labels. Change components only in an area known to be non-hazardous.
Performing these procedures in a hazardous area could result in
personal injury or property damage.
To avoid circuit damage when working inside the unit, use appropriate
electrostatic discharge precautions, such as wearing a grounded wrist
strap.
To replace the battery pack:
1.
Unscrew the front end (LCD end) cap cover.
2.
Place the power jumper (located at J1 on the Battery Charger
module) in the OFF position.
3.
Remove the ribbon cable from the Battery Charger module to the
Backplane Board.
4.
Remove the four screws from the Battery Charger module.
5.
Remove the Battery Charger module.
Replace the Battery Charger module.
6.
Replace the four screws from the Battery Charger module.
7.
Replace the ribbon cable from the Backplane Board to the Battery
8.
Charger Board.
Place the power jumper (located at J1 on the Battery Charger
9.
module) in the ON position.
Replace the front end cap cover. Screw the cover on until metal
10.
contacts metal. Do not over-tighten the cover.
Power Connections
FloBoss 103/104 Instruction Manual
" as described in Section 3.3, Determining Power
SF
amps  Reserve hrs = _____ amp-hrs
SF
3-7