Specifications of Basic I/O Units and High-density I/O Units
Note Terminal numbers A0 to A9 and B0 to B9 are used in this manual, but they are not printed on the Unit.
C200H-OA221 Triac Output Unit (8 Points)
Circuit Configuration
Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as
work bits.
Terminal Connections
Max. Switching Capacity
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Weight
Output indicator
Internal
circuits
Fuse blowout
detection circuit
F indicator
Fuse: 5 A 250 V (5.2-dia. x 20) MF51SH (JIS)
250 V AC max.
(1 A max. 4 A/Unit)
1 A 250 V AC, 50/60 Hz (4 A/Unit)
10 mA (resistive load)/40 mA (inductive load) 10 V
AC
3 mA (100 V AC) max./6 mA (200 V AC) max.
1.2 V max.
1 ms max.
1/2 of load frequency or less.
1 (8 points/common)
140 mA 5 V DC max.
5 A 250 V (5.2-dia. × 20)
250 g max.
OUT
L
OUT
L
Fuse
COM
250 V AC max.
0
L
A0
1
A1
L
2
A2
L
3
A3
L
4
A4
L
5
A5
L
6
A6
L
7
A7
L
A8
COM
A9
NC
Appendix A
637