Mitsubishi Electric MELSEC iQ-F Reference page 40

Fx5 ethernet/cc-link ie function block
Hide thumbs Also See for MELSEC iQ-F:
Table of Contents

Advertisement

■Public label
No.
Variable name
(10)
pbi_bReadTiming
(11)
pbi_uMonitorTime
(12)
pbo_uResendCount
(13)
pbo_u4ErrTime
(14)
pbo_uErrNetworkNo
(15)
pbo_uErrStationNo
(16)
pbo_uSendNetwork
No
(17)
pbo_uSendStationN
o
(18)
pbo_uSendChannel
3 CC-LINK IE FIELD NETWORK MODULE FB
38
3.4 M+FX5CCLIEF_Recv
Name
Data type
Read timing
Bit
Arrival monitoring
Word [unsigned]
time
Number of resends
Word [unsigned]
Error occurrence time
Word [unsigned]
(0..3)
Error detection
Word [unsigned]
network number
Error-detected station
Word [unsigned]
number
Send station network
Word [unsigned]
number
Send station number
Word [unsigned]
Channel used by
Word [unsigned]
send station
Default value
Description
This label is not used in the FB program and does not
need to be set.
Data is read at the first END processing after the unit FB
is started.
0, 1 to 32767
Specify the time to monitor until completion of the
process. If the processing is not completed within the
monitoring time, it will end with an error.
0: 10 s
1 to 32767: 1 to 32767 s
This label is not used in the FB program and does not
need to be set.
Clock data at the time of error occurrence is stored.
1st word
• Upper 8 bits: Month (01H to 12H)
• Lower 8 bits: Lower 2 digits of year (00H to 99H)
2nd word
• Upper 8 bits: Hour (00H to 23H)
• Lower 8 bits: Day (01H to 31H)
3rd word
• Upper 8 bits: Second (00H to 59H)
• Lower 8 bits: Minute (00H to 59H)
4th word
• Upper 8 bits: Upper 2 digits of year (00H to 99H)
• Lower 8 bits: Day of week (00H (Sunday) to 06H
(Saturday))
The network number of the station in which an error was
detected is stored.
The station number of the station in which an error was
detected is stored.
CC-Link IE Field Network station number
• 125: Master station
• 1 to 120: Local station, remote device station,
intelligent device station, submaster station
The network number of the send station is stored.
The station number of the send station is stored.
CC-Link IE Field Network station number
• 125: Master station
• 1 to 120: Local station, remote device station,
intelligent device station, submaster station
1 to 8
The channel number used by the send station is stored.

Advertisement

Table of Contents
loading

Table of Contents