3.3

M+FX5CCLIEF_Send

Name
M+FX5CCLIEF_Send
Overview
Item
Description
Overview
Sends data to the programmable controller of another station.
Symbol
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
Labels
■Input label
No.
Variable name
Name
(1)
i_bEN
Execution command
(2)
i_stModule
Module label
(3)
i_uTargetNetworkNo
Target network
number
(4)
i_uTargetStationNo
Target station number
(5)
i_uChannel
Own station channel
(6)
i_uTargetChannel
Target station data
storage channel
M+FX5CCLIEF_Send
B
:
i_bEN
DUT
:
i_stModule
UW
:
i_uTargetNetworkNo
UW :
i_uTargetStationNo
UW i_uChannel
:
UW i_uTargetChannel
:
UW i_uDataLength
:
UW i_uSendData
:
(13) pbi_uTargetStation
(14) pbi_bArrivalConfirm
(15) pbi_uResendCountMax
(16) pbi_uMonitorTime
(17) pbo_uResendCount
(18) pbo_u4ErrTime
(19) pbo_uErrNetworkNo
(20) pbo_uErrStationNo
Data type
Bit
Structure
Word [unsigned]
Word [unsigned]
Word [unsigned]
Word [unsigned]
o_bENO
:
B
(9)
o_bOK
:
B
(10)
o_bErr
:
B
(11)
o_uErrId
:
UW
(12)
Range
Description
ON, OFF
ON: The FB is activated.
OFF: The FB is not activated.
The setting range
Specify the module label of the FX5-CCLIEF.
differs depending on
the module label.
1 to 239
Specify the network number of the target station.
Specify the station number of the target station or the
transient transmission group number.
■When "target station specification method" is set to 0
to specify a station number
CC-Link IE Field Network station number
• 125: Master station
• 126: Master operating station
• 1 to 120: Local station, remote device station,
intelligent device station, submaster station
■When "target station specification method" is set to 1
to specify a group
Specify the transient transmission group number
• 1 to 32
■When "target station specification method" is set to 2
to specify all stations
The setting is ignored.
1, 2
Specify the channel to be used by own station.
1 to 8
Specify the channel of the target station for storing data.
When the target station is a CC-Link IE Field Network
master/local module, specify 1 or 2.
3 CC-LINK IE FIELD NETWORK MODULE FB
3.3 M+FX5CCLIEF_Send