Fx5 ethernet/cc-link ie function block
Hide thumbs Also See for MELSEC iQ-F:
Table of Contents

Advertisement

Item
Timing chart of I/O signals
Restrictions or precautions
Error code
Error code (hexadecimal)
D000H to DFFFH
3 CC-LINK IE FIELD NETWORK MODULE FB
36
3.3 M+FX5CCLIEF_Send
Description
[For normal completion]
i_bEN
o_bENO
GP.SEND instruction
Stop
o_bOK
o_bErr
o_uErrId
[For error completion]
(For instruction error)
i_bEN
o_bENO
GP.SEND instruction Stop
o_bOK
o_bErr
o_uErrId
• This FB does not include the error recovery processing. Program the error recovery processing separately in accordance
with the required system operation.
• This FB uses the G(P).SEND instruction.
• Turn off i_bEN (Execution command) after o_bOK (Normal completion) or o_bErr (Error completion) is turned on. By turning
off i_bEN (Execution command), o_bOK (Normal completion) or o_bErr (Error completion) is turned off and o_uErrId (Error
code) is cleared to 0. However, because the GP.SEND instruction which is a pulse instruction in the FB is used, if a write is
performed while the FB is executed, the instruction may not be executed, and o_bOK (Normal completion) and o_bErr (Error
completion) may not turn on. If this happens, turn i_bEN (Execute command) from off to on again.
• This FB cannot be used in an interrupt program.
• Do not use this FB in programs that are executed only once, such as a subroutine program or FOR-NEXT loop, because
i_bEN (Execution command) cannot be turned off and the normal operation cannot be acquired. Always use this FB in
programs that can turn off i_bEN (Execution command).
• When using several of these FBs, make sure that the target station address and own station channel do not overlap.
• Every input must be provided with a value for proper FB operation.
• Set the module parameters in GX Works3 in accordance with the connected equipment and system. For the module
parameters, refer to the MELSEC iQ-F FX5 User's Manual (CC-Link IE).
Description
This error code is the same as the error code that occurs with the
(GP.SEND) instruction for sending data to the programmable
controller of another station.
Execution
0H
Execution
Stop
0H
Error code
Stop
0H
Action
Refer to the MELSEC iQ-F FX5 User's Manual
(CC-Link IE)